
495
Description
CDH EGD fault detected by the T processor
Possible Cause
•
CDH EGD producer is powered down
•
Producer is unhealthy
•
Ethernet connection(s) failure
Solution
•
Ensure all EGD producers are powered up and healthy.
•
Check for a defective Ethernet cable from producer to network switch. Replace the cable(s).
•
Check for a defective network switch by placing the producer's Ethernet cable into an empty port. If the problem persists,
replace the network switch.
•
Replace the producer processor module.
496
Description
Failed to incorporate the user-configured frame state timeouts
Possible Cause
•
Invalid user-configured frame state timeout values
•
Failed to parse the user-configured frame state timeouts file
Solution
•
Timeout values configured by the user must satisfy the condition
Frame Rate > Output Timeout > App Timeout > Input Timeout > 0
.
•
Rebuild the application and force an offline download of the application to the controller.
497-498
Description
Fan loss detected for controller fan [ ]
Possible Cause
•
Hardware malfunction
•
Fan power not applied
Solution
•
Check the fan.
•
Verify that the power connector is properly inserted.
•
Replace the fan.
64
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information