Important
Before configuring a channel to operate as a Discrete Input, check the status of the remote input
device and the actions assigned to the Discrete Input. If the Discrete Input is ON, all actions assigned
to the Discrete Input will be performed when the new channel configuration is implemented. If this is
not acceptable, change the state of the remote device or wait to configure the channel as a Discrete
Input until an appropriate time.
Procedure
1.
Set Channel B as desired.
Option
Description
Secondary mA Output
Channel B will operate as an mA Output.
Frequency Output
Channel B will operate as a Frequency Output.
Discrete Output
Channel B will operate as a Discrete Output.
2.
If you set Channel B to operate as a Frequency Output or Discrete Output, configure
the power source for the channel.
Option
Description
Internal (Active)
The channel is powered by the transmitter.
External (Passive)
The channel is powered by an external power source.
3.
Set Channel C as desired.
Option
Description
Frequency Output
Channel C will operate as a Frequency Output.
Discrete Output
Channel C will operate as a Discrete Output.
Discrete Input
Channel C will operate as a Discrete Input.
4.
Configure the power source for Channel C.
Option
Description
Internal (Active)
The channel is powered by the transmitter.
External (Passive)
The channel is powered by an external power source.
Postrequisites
For each channel that you configured, perform or verify the corresponding input or output
configuration. When the configuration of a channel is changed, the channel’s behavior will
be controlled by the configuration that is stored for the selected input or output type, and
the stored configuration may not be appropriate for your process.
Integrate the meter with the control system
76
Micro Motion Model 2500 Transmitters with Configurable Input/Outputs
Summary of Contents for Micro Motion 2500
Page 8: ...Contents vi Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Page 10: ...Getting started 2 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Page 18: ...Quick start 10 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...