Alert num-
ber
Alert title
Possible cause
Recommended actions
A013
Zero Calibration
Failed: Unstable
There was too much process insta-
bility during the calibration proce-
dure.
This alert will not clear until you cy-
cle power to the meter.
•
Remove or reduce sources of electro-
mechanical noise (e.g., pumps, vibra-
tion, pipe stress), cycle power to the
meter, then retry the procedure.
A014
Transmitter Failure
Many possible causes.
This alert often occurs in conjunc-
tion with alerts A9 and A26.
•
Ensure that all wiring compartment
covers are installed correctly.
•
Ensure that all transmitter wiring meets
specifications and that all cable shields
are properly terminated.
•
Check the grounding of all compo-
nents.
•
Evaluate the environment for sources of
high electromagnetic interference
(EMI) and relocate the transmitter or
wiring as necessary.
•
Contact customer support.
A016
Sensor Temperature
(RTD) Failure
The value computed for the resist-
ance of the line RTD is outside lim-
its.
•
Check your process conditions against
the values reported by the device.
•
Check the wiring between the sensor
and the transmitter.
•
Verify that internal wiring is secure and
that there are no internal electrical
problems.
•
Contact customer support.
A017
Sensor Case Tem-
perature (RTD) Fail-
ure
The values computed for the resist-
ance of the meter and case RTDs
are outside limits.
•
Check your process conditions against
the values reported by the device. Tem-
perature should be between –200 °F
and +400 °F.
•
Verify all of the characterization or cali-
bration parameters. See the sensor tag
or the calibration sheet for your meter.
•
Check the wiring between the sensor
and the transmitter.
•
Verify that internal wiring is secure and
that there are no internal electrical
problems.
•
Contact customer support.
A020
Calibration Factors
Missing
Some calibration factors have not
been entered or are incorrect.
•
Verify all of the characterization or cali-
bration parameters. See the sensor tag
or the calibration sheet for your meter.
•
Verify the setting of the Sensor Type pa-
rameter.
•
If Sensor Type=
Curved Tube
, ensure that
no parameters specific to
Straight Tube
have been set.
Troubleshooting
Configuration and Use Manual
165
Summary of Contents for Micro Motion 2500
Page 8: ...Contents vi Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Page 10: ...Getting started 2 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Page 18: ...Quick start 10 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Page 237: ...NE 53 history Configuration and Use Manual 229 ...