6
Integrate the meter with the control
system
Topics covered in this chapter:
•
Configure the transmitter channels
•
•
Configure the Frequency Output
•
•
•
•
Configure digital communications
6.1
Configure the transmitter channels
ProLink III
Device Tools > Configuration > I/O > Channels
Field Communicator Configure > Manual Setup > Inputs/Outputs > Channels > Channel B
Configure > Manual Setup > Inputs/Outputs > Channels > Channel C
Overview
You can configure the channels on your transmitter to operate in several ways. The
channel configuration must match the wiring at the transmitter terminals.
Note
Channel A always operates as an internally-powered mA Output. If Channel B is configured as an mA
Output, it is internally powered.
Important
If you need both a Frequency Output and a Discrete Output, you must first configure Channel B as
the Frequency Output, then configure Channel C as the Discrete Output. Other combinations are
invalid and will be rejected by the transmitter.
Prerequisites
To avoid causing process errors:
•
Configure the channels before configuring the outputs.
•
Before changing the channel configuration, ensure that all control loops affected by
the channel are under manual control.
Integrate the meter with the control system
Configuration and Use Manual
75
Summary of Contents for Micro Motion 2500
Page 8: ...Contents vi Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Page 10: ...Getting started 2 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Page 18: ...Quick start 10 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Page 237: ...NE 53 history Configuration and Use Manual 229 ...