6.7
Configure digital communications
The digital communications parameters control how the transmitter will communicate
using digital communications.
Your transmitter supports the following types of digital communications:
•
HART/Bell 202 over the primary mA terminals
•
Modbus/RS-485 over the RS-485 terminals
•
Modbus RTU via the service port
Note
The service port responds automatically to a wide range of connection requests. It is not
configurable.
6.7.1
Configure HART/Bell 202 communications
HART/Bell 202 communications parameters support HART communications with the
transmitter's primary mA terminals over a HART/Bell 202 network.
Configure basic HART parameters
Basic HART parameters include the HART address, HART tags, and the operation of the
primary mA Output.
HART/Bell 202 communications parameters support HART communication with the
transmitter's primary mA terminals over a HART/Bell 202 network. The HART/Bell 202
communications parameters include:
•
HART Address (Polling Address)
•
mA Output Action
•
Burst Parameters (optional)
•
HART Variables (optional)
Procedure
1.
Set HART Address to a value that is unique on your network.
•
Default: 0
•
Range: 0 to 15
Tips
•
The default address is typically used unless you are in a multidrop environment.
•
Devices using HART protocol to communicate with the transmitter may use either HART
Address or HART Tag (Software Tag) to identify the transmitter. Configure either or both,
as required by your other HART devices.
2.
Ensure that mA Output Action is configured appropriately.
Integrate the meter with the control system
Configuration and Use Manual
103
Summary of Contents for Micro Motion 2500
Page 8: ...Contents vi Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Page 10: ...Getting started 2 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Page 18: ...Quick start 10 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Page 237: ...NE 53 history Configuration and Use Manual 229 ...