CAUTION!
If you set mA Output Fault Action or Frequency Output Fault Action to
None
, be sure to set
Digital Communications Fault Action to
None
. If you do not, the output will not report actual
process data, and this may result in measurement errors or unintended consequences for your
process.
Restriction
If Digital Communications Fault Action is set to
NAN
(not a number), you cannot set mA Output Fault
Action or Frequency Output Fault Action to
None
. If you try to do this, the transmitter will not accept
the configuration.
Integrate the meter with the control system
112
Micro Motion Model 2500 Transmitters with Configurable Input/Outputs