Option
Setup
Polling for tempera-
ture
a. Ensure that the primary mA output has been wired to support
HART polling.
b. Choose Online > Configure > Manual Setup > Measurements .
c. Click External Inputs.
d. Click Next.
e. Enable External Temperature.
f. Click Next.
g. Choose an unused polling slot.
h. Set Poll Control to
Poll As Primary Host
or
Poll as Secondary Host
.
i. Set External Tag to the HART tag of the external temperature de-
vice.
j. Set Polled Variable to
Temperature
.
Tip
•
Poll as Primary
: No other HART masters will be on the network.
•
Poll as Secondary
: Other HART masters will be on the network.
The Field Communicator is not a HART master.
A value written by
digital communica-
tions
a. Choose Online > Configure > Manual Setup > Measurements >
External Pressure/Temperature > Temperature .
b. Enable External Temperature.
c. Perform the necessary host programming and communications
setup to write temperature data to the transmitter at appropri-
ate intervals.
Note
If the Weights & Measures application is implemented and the trans-
mitter is secured, digital communications cannot be used to write
temperature or pressure data to the transmitter.
(1) Not available on all transmitters.
8.
Choose Online > Configure > Manual Setup > Measurements > Conc Measurement
(CM) > CM Configuration and set Active Matrix to the matrix to be used for
measurement.
Concentration process variables are now available on the transmitter. You can view and
report them in the same way that you view and report other process variables.
4.8.3
Standard matrices for the concentration measurement
application
The standard concentration matrices available from Micro Motion are applicable for a
variety of process fluids. These matrices are included in the ProLink III installation.
Configure process measurement
Configuration and Use Manual
55
Summary of Contents for Micro Motion 2500
Page 8: ...Contents vi Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Page 10: ...Getting started 2 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Page 18: ...Quick start 10 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Page 237: ...NE 53 history Configuration and Use Manual 229 ...