8-30
BE1-CDS240 Application
9365200990 Rev F
State Labels
Input Purpose Name
Label
Energized De-Energized
IN7
Breaker Failure Initiate by external relays with
fault detector supervision. Typically used for
overcurrent tripping relays.
EXT-BFI-50-
SUPV
INI NORMAL
IN8
Puts the relay in test mode so that the breaker
failure is disabled when Input 8 is de-energized.
TEST-MODE-
DISABL
NORMAL TSTMODE
Table 8-21. CDS240-TXBU-B-BE Function Block Logic
Function Purpose
BESTlogic
Expression
Mode
Setting
87
Used for percent-restrained differential protection with high-speed
unrestrained instantaneous differential protection. Differential function
is blocked when Virtual Switch 43 is TRUE.
43 1
(enabled)
51N
Used for timed ground overcurrent protection for independent ground
input circuit.
0
G (Ground
Input)
151P
Used for timed phase overcurrent protection for CT input
circuit 1.
0
1 (Circuit 1)
151N
Used for timed neutral overcurrent protection for CT input
circuit 1.
0
1 (Circuit 1)
151Q
Used for timed negative-sequence overcurrent protection for CT input
circuit 1.
0
1 (Circuit 1)
251P
Used for timed phase overcurrent protection for CT input circuit 2.
0
2 (Circuit 2)
251N
Used for timed neutral overcurrent protection for CT input
circuit 2.
0
2 (Circuit 2)
251Q
Used for timed negative-sequence overcurrent protection for CT input
circuit 2.
0
2 (Circuit 2)
50TP
Used as fault detector for Breaker 2 external BFI (IN7) supervision.
0
2 (Circuit 2)
50TN
Used as fault detector for Breaker 2 external BFI (IN7) supervision.
0
2 (Circuit 2)
50TQ
Used as fault detector for Breaker 2 external BFI (IN7) supervision.
0
2 (Circuit 2)
250TP
Used for bus backup overcurrent protection, CT Circuit 2.
0
2 (Circuit 2)
250TN
Used for bus backup overcurrent protection, CT Circuit 2.
0
2 (Circuit 2)
250TQ
Used for bus backup overcurrent protection, CT Circuit 2.
0
2 (Circuit 2)
BFI50 Logic:
Used for CT Circuit 2 breaker failure protection. Initiated
by BFI with fault detector supervision expression.
VO10
BFI52 Logic:
Not used.
0
52 STATUS Logic:
Not used.
0
150BF
BLK Logic:
Block breaker failure protection when relay is in test mode.
VO15
1 (enable)
INI Logic:
Used for breaker failure tripping with no current supervision.
VO9
62
BLK Logic:
Block breaker failure protection when relay is in test mode.
VO15
1 (PU/DO)
Input 0 Logic:
Switch to setting group 1 if feeder relay is out of service
as indicated by open contact (IN5).
/IN5
Input 1 Logic:
No manual selection logic is used.
0
Input 2 Logic:
No manual selection logic is used.
0
Input 3 Logic:
No manual selection logic is used.
0
GROUP
Auto/Manual Logic:
No automatic selection.
0
2 (Binary
Inputs)
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......