Table 13-46. Instantaneous 50T Element Test Values
Sensing Input Type
Phase
Negative-Sequence
Neutral
Comments
S0-50TP=0.5,0 S0-50TQ=0,0 S0-50TN=0.5,0
Note
1
S0-50TP=5.0,0 S0-50TQ=1.67,0 S0-50TN=5.0,0 Note
2
5 A
S0-50TP=25.0,0 S0-50TQ=8.33,0 S0-50TN=25.0,0 Note
2
S0-50TP=0.1,0 S0-50TQ=0,0 S0-50TN=0.1,0
Note
1
S0-50TP=1.0,0 S0-50TQ=0.33,0 S0-50TN=1.0,0 Note
2
1 A
S0-50TP=5.0,0 S0-50TQ=1.67,0 S0-50TN=5.0,0 Note
2
Notes for Table 13-46:
1.
Sets 50TP and 50TN to pickup at 0.5 amperes test current and 50TQ is disabled.
2.
Sets all 50T<x> to pickup at 0.5 amperes test current.
3.
See Sidebar 13-10 for more information on negative-sequence pickup.
Step 4:
Slowly ramp up current on the phase A input until OUT1, OUT2, and OUT3 close. (In
accordance with Note 1 for Table 13-46, OUT3 will not close when 50TQ is disabled.) Verify
that pickup occurred within the specified accuracy of the relay as listed in Table 13-47.
Table 13-47. Instantaneous 50T Element Accuracy
Sensing Type
Pickup Accuracy - Phase and Neutral
A or B (1 ampere nominal systems)
2% of setting or
10 milliamperes
D, E, or F (5 ampere nominal systems)
2% of setting or
50 milliamperes
Step 5:
After pickup occurs, slowly ramp the current down until OUT1, OUT2 and OUT3 open. Verify
that dropout occurred as specified (95%
2%).
Step 6:
Repeat Steps 3, 4, and 5 for all values in Table 13-47. Optionally, reconnect the current
source to B-phase (A5*, A6) and C-phase (A7* A8) inputs to test the response of all phases
for each succeeding test.
Step 7:
(Optional.) Repeat Steps 3 through 6 for phases B and C of the relay unless each phase was
tested in Step 4. If so, skip this step and proceed to Step 8.
Step 8:
(Optional.) Repeat Steps 1 through 7 for the 150T, 250T, 350T, 450T, 550T, 650T, and 750T
elements. Use Table 13-48 or 13-49 as a reference for substituting the commands used in
Step 1.
Table 13-48. Instantaneous Overcurrent 150T Element Test Logic
Replace These Commands
With These Commands For 150T Element Tests
SL-50T=1,0 SL-150T=1,0
SL-VO1=50TPT SL-VO1=150TPT
SL-VO2=50TNT SL-VO2=150TNT
SL-VO3=50TQT SL-VO3=150TQT
SG-TARG=50T SG-TARG=150T
SG-TRIGGER=50TPT+50TNT+50TQT,
50TQPU,0
SG-TRIGGER=150TQT,
150TQTPU,0
13-58
BE1-CDS240 Testing and Maintenance
9365200990 Rev F
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......