6-40
BE1-CDS240 Reporting and Alarm Functions
9365200990 Rev F
I.D. #
Name
Description
6
BKR 2 FAIL ALARM
Breaker Failure Initiate > Control Time (150BF).
7
BKR 3 FAIL ALARM
Breaker Failure Initiate > Control Time (250BF).
8
BKR 4 FAIL ALARM
Breaker Failure Initiate > Control Time (350BF).
9
DIFFERENTIAL ALARM
Differential threshold exceeded.
10
CHANGES LOST ALARM
Password access lost. No changes saved.
11
BREAKER ALARM 1
Breaker Alarm 1 threshold (SA-BKR1 setting) exceeded.
12
BREAKER ALARM 2
Breaker Alarm 2 threshold (SA-BKR2 setting) exceeded.
13
BREAKER ALARM 3
Breaker Alarm 3 threshold (SA-BKR3 setting) exceeded.
14
BREAKER ALARM 4
Breaker Alarm 4 threshold (SA-BKR4 setting) exceeded.
15
BREAKER ALARM 5
Breaker Alarm 5 threshold (SA-BKR5 setting) exceeded.
16
BREAKER ALARM 6
Breaker Alarm 6 threshold (SA-BKR6 setting) exceeded.
17
BREAKER ALARM 7
Breaker Alarm 7 threshold (SA-BKR7 setting) exceeded.
18
BREAKER ALARM 8
Breaker Alarm 8 threshold (SA-BKR8 setting) exceeded.
19
BREAKER ALARM 9
Breaker Alarm 9 threshold (SA-BKR9 setting) exceeded.
20
BREAKER ALARM 10
Breaker Alarm 10 threshold (SA-BKR10 setting) exceeded.
21
BREAKER ALARM 11
Breaker Alarm 11 threshold (SA-BKR11 setting) exceeded.
22
BREAKER ALARM 12
Breaker Alarm 12 threshold (SA-BKR12 setting) exceeded.
23
GROUP OVERRIDE ALARM
Setting Group override in effect.
24
SYS I/O DELAY ALARM
Excessive delay in HMI or serial communication operation.
25
COMM ERROR ALARM
Communication failure.
26
CLOCK ERROR ALARM
Real-time clock not set.
27
uP RESET ALARM
Microprocessor has been reset.
28
SETTING CHANGE ALARM
Setting change made by user.
29
EE NON-FATAL ERR ALARM
EEPROM nonfatal recoverable error.
30
OUTPUT OVERRIDE ALARM
One or more output contacts have logic override condition.
31
IRIG SYNC LOST ALARM
Loss of IRIG synchronization.
32
SGC ACTIVE ALARM
Active setting group changed.
33
VO13_LABEL
VO13 logic is TRUE (user programmable logic alarm).
34
VO14_LABEL
VO14 logic is TRUE (user programmable logic alarm).
35
VO15_LABEL
VO15 logic is TRUE (user programmable logic alarm).
36
FLT RPT TIMEOUT ALARM
TRUE if fault event trigger lasts longer than 60 seconds.
37
TRANSFORMER ALARM 1
Transformer Alarm 1 threshold (SA-TX1 setting) exceeded.
38
TRANSFORMER ALARM 2
Transformer Alarm 2 threshold (SA-TX2 setting) exceeded.
39
TRANSFORMER ALARM 3
Transformer Alarm 3 threshold (SA-TX3 setting) exceeded.
40
TRANSFORMER ALARM 4
Transformer Alarm 4 threshold (SA-TX4 setting) exceeded.
41
TRANSFORMER ALARM 5
Transformer Alarm 5 threshold (SA-TX5 setting) exceeded.
42
TRANSFORMER ALARM 6
Transformer Alarm 6 threshold (SA-TX6 setting) exceeded.
43
TRANSFORMER ALARM 7
Transformer Alarm 7 threshold (SA-TX7 setting) exceeded.
44
TRANSFORMER ALARM 8
Transformer Alarm 8 threshold (SA-TX8 setting) exceeded.
45
LOGIC = NONE ALARM
Active Logic=NONE. No logic selected.
46
PHASE DEMAND 1 ALARM
Circuit 1 Phase Current Demand threshold exceeded.
47
PHASE DEMAND 2 ALARM
Circuit 2 Phase Current Demand threshold exceeded.
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......