BE1-CDS240 General Information
1-21
#50TQ:
±0.5% or ±1 cycle, whichever is greater, plus trip
time for instantaneous response (0.0 setting)
Trip Time for 0.0 Delay Setting
#50TP, #50TN:
1¼ cycles maximum for current 5 times the pickup
setting.
2 cycles maximum for current 1.5 times pickup.
4 cycles maximum for current 1.05 times the
pickup setting
#50TQ:
2¼ cycles maximum for current 5 times the pickup
setting.
3 cycles maximum for current 1.5 times pickup.
5 cycles maximum for current 1.05 times the
pickup setting.
Time Overcurrent Functions
Current Pickup, Phase, and Neutral (#51P, #51N)
Dropout/pickup ratio:
95% of pickup value
Pickup Accuracy
5 Ampere CT:
±2% or ±50 mA
1 Ampere CT:
±2% or ±10 mA
Current Pickup, Negative-Sequence (#51Q)
Dropout/pickup ratio:
95% of pickup value
Pickup Accuracy
5 Ampere CT:
±3% or ±75 mA
1 Ampere CT:
±3% or ±15 mA
Current Input All 51 Functions
5 Ampere CT
Range:
0.50 to 16.0 A
Increment:
0.01 from 0.50 to 9.99 A
0.1 from 10.0 to 16.0 A
1 Ampere CT
Range:
0.10 to 3.20 A
Increment:
0.01
A
Time Current Characteristic Curves
Timing Accuracy (All 51 Functions):
Within ±5% or ±1½ cycles, whichever is greater
for time dial settings greater than 0.1 and
multiples of 2 to 40 times the pickup setting, but
not over 150 A for 5 A current sensing units or 30
A for 1 A current sensing units. See Appendix A
for information on available timing curves.
Volts/Hz (24)
Pickup
Range:
0.5
to
6
V/Hz
Accuracy: ±2%
Integrating Time Delay
Time Dial:
0.0 to 9.9 V/Hz
Reset Dial:
0.0 to 9.9 V/Hz
Accuracy:
5% or 4 cycles, whichever is greater
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......