function (SB-LOGIC). Figure 6-10 illustrates breaker status (SB-LOGIC) during a fault and protective trip.
Table 6-11 serves as a legend for the call-outs of Figure 6-10.
The relay sums the N
th
power of the currents that are interrupted and will set the breaker duty alarm when
the sum exceeds the N
th
power of the maximum breaker duty (D
max
) setting. The user must enter a value
for N and a value for D
max
.
To determine N and D
max
, the user needs to find two measurements of allowable breaker wear. These
levels would typically be the maximum number of operations at load level currents and the maximum
number of operations at maximum fault rating.
Point 1; # Ops @
Imax load
Point 2; # Ops @ I
max fault
To determine the breaker wear exponent N, using the above data points as an example, apply this
equation:
load
max
fault
max
fault
max
load
max
I
I
log
I
@
Ops
#
I
@
Ops
#
log
N
N can be any value from 1 to 3.
Using values for I
max load
and I
max fault
in primary amperes (the relay multiplies by the CTR before doing
calculations), the value for maximum breaker duty, D
max
, is calculated from either of these two equations:
1/N
load
max
N
load
max
max
I
@
Ops
#
I
D
1/N
fault
max
N
fault
max
max
I
@
Ops
#
I
D
Both of the last two equations should yield the same value for D
max
.
When testing the relay by injecting currents into the relay, the values in the duty registers should be read
and recorded prior to the start of testing. Once testing is complete and the relay is returned to service, the
registers should be reset to the original pre-test values. A block accumulation logic input may be used
when testing so that simulated breaker duty is not added to the duty registers. The BLKBKR logic function
is an OR logic term (e.g., IN1 or VO7) which blocks the breaker monitoring logic when TRUE (1).
BLKBKR is set to zero to disable blocking. When breaker monitoring is blocked (logic expression equals
1), breaker duty is not accumulated.
6-20
BE1-CDS240 Reporting and Alarm Functions
9365200990 Rev F
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......