13-90
BE1-CDS240 Testing and Maintenance
9365200990 Rev F
Command Purpose
CS-43=1
Selects Setting Group 0 for operation.
CO-43=1
Executes Setting Group 0 for operation.
CS-43=0
Deselects Setting Group 0 for operation.
CO-43=0
Executes Deselecting Setting Group 0 for operation.
CS-243=1
Selects Setting Group 2 for operation.
CO-243=1
Executes Setting Group 2 for operation.
CS-243=0
Deselects Setting Group 2 for operation.
CO-243=0
Executes Deselecting Setting Group 2 for operation.
CS-343=1
Selects Setting Group 3 for operation.
CO-343=1
Executes Setting Group 3 for operation.
E Exit.
Y Save
settings
Step 4:
Using the RS-LGC command to retrieve logic variable data from the SER, verify that the
setting group change actions were logged.
Manual Change Mode 2
Manual Change Mode 2 test procedures are a continuation of the Mode 1 test procedures. Do not change
the logic or settings except for those in Step 1 and subsequent.
Step 1: Send to the relay the commands in Table 13-116.
Table 13-116. Binary Group Control Selection Setup
Command Purpose
A= Gain
access.
SL-
GROUP=2
Sets setting group control function to binary coded selection (AUTO logic is unchanged
from Table 13-80).
E Exit.
Y Save
settings.
Step 2:
Verify that relay Outputs OUT3 opened when the commands in Table 13-113 were completed
and OUT1 and OUT2 remained open. With the existing logic and discrete select enabled, D0
and D1 inputs are FALSE, and D2 and D3 inputs have no effect on setting group selection.
For more information on setting group selection, see Section 4,
Protection and Control
Functions, Setting Groups.
Step 3:
Verify that SG0 is the active setting group by sending the command RG-GRPACTIVE to the
relay. It should echo back that the SG0 is the active group. Using the HMI, you may also verify
the active setting group at the front panel interface Screen \STAT\OPER\ACTIVEG, 1.4.4.
Step 4: Send to the relay the commands in Table 13-117.
Table 13-117. Binary Group Control Selection Test Commands
Command Purpose
A= Gain
access.
CS-43=1
Selects Setting Group 1 for operation.
CO-43=1
Executes Setting Group 1 for operation (D0=1).
CS-43=0
Deselects Setting Group 1 for operation.
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......