
You may also use the average restraint operating characteristic and test the relay by decreasing one
current from a balanced condition. For additional information on testing in this manner, see Sidebar 13-7.
Sidebar 13-7. Average Restraint when Decreasing One Input from Balance
A second way to test the restrained pickup of the BE1-CDS240 relay is to decrease one of two currents,
initially applied in balance to create an imbalance. In this narrative, Input 1 current will be the input to be
changed. A similar analysis can be made for changing Input 2 current.
By decreasing the input current I
1
from balance, the value of I
1trip
is defined as:
I
1trip
= I
2balance
(1- ((2*
100
slope
)/(2+
100
slope
)))
in per unit
with the minimum trip point established as:
I
1trip min
= I
2balance
– minpu in per unit
where: minpu is the minimum pickup setting
Under test and in-service conditions, the following equations determine whether the relay operates along
the flat minimum pickup or slope of the operating characteristic. If
I
restraint at balance
> minpu x
2
/
1
100
/
1
slope
in per unit, use the 1
st
equation, or if
I
restraint at balance
< minpu x
2
/
1
100
/
1
slope
in per unit, use the 2
nd
equation.
Step 13: Send the commands listed in Table 13-28 to the relay.
Table 13-28. Setup Commands
Command Purpose
A= Gain
access
S#-
87=0.35,15,0,0,0,1
Minpu = 0.35, slope = 15% (of average restraint), 2
nd
= disabled, 5
th
= disabled,
URO= disabled, 2
nd
harmonic sharing =1 (yes)
E Exit
Y Save
settings
Step 14: Apply balancing current to phase A Input 1 and phase A Input 2 at the magnitude indicated in
each row of either Table 13-29 (5 ampere sensing) or 13-25 (1 ampere sensing) and slowly
increase phase A Input 1 until OUT1 closes. Reference the corresponding table to verify
pickup accuracy.
13-44
BE1-CDS240 Testing and Maintenance
9365200990 Rev F
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......