At the top center of the
BESTlogic Function Element
screen is a pull-down menu labeled
Logic
. This
menu allows viewing of the BESTlogic settings for each preprogrammed logic scheme. A custom logic
scheme must be created and selected in the
Logic
pull-down menu at the top of the screen before
BESTlogic settings can be changed. See Section 7,
BESTlogic Programmable Logic
.
Enable the BESTlogic function by selecting its mode of operation from the
Mode
pull-down menu. To
connect the function/elements inputs, select the button for the corresponding input in the
BESTlogic
Function Element
screen. The
BESTlogic Expression Builder
screen will open. Select the expression type
to be used. Then, select the BESTlogic variable, or series of variables to be connected to the input.
Select
Save
when finished to return to the
BESTlogic Function Element
screen. For more details on the
BESTlogic Expression Builder
, See Section 7,
BESTlogic Programmable Logic
. Select
Done
when the
settings have been completely edited.
Table 4-19 lists the BESTlogic settings for Volts per Hertz Overexcitation.
Table 4-19. BESTlogic Settings for Volts per Hertz Overexcitation
Function Range/Purpose Default
Mode
0 = Disable
1 = Enable
0
BLK
Logic expression that disables the function when TRUE.
0
Operating Settings for Volts per Hertz Overexcitation
Operating settings for the 24 function consist of a pickup setting, a trip time dial, and a reset time dial. A
pickup of 0 disables the element. The unit of measure is secondary VPP/Hz or VPN/Hz and depends on
the SG-VTP setting. For more information, refer to Section 3,
Input and Output Functions, Power System
Inputs
. Operating settings are made using BESTCOMS. Figure 4-32 illustrates the BESTCOMS screen
used to select operational settings for the
Volts per Hertz
element. To open the screen, select
Voltage
Protection
from the
Screens
pull-down menu and select the
24
Tab. Alternately, settings can be made
using the S<g>-24 and S<g>-24D commands or at the optional front panel HMI using Screen 5.#.5.1,
\PROT\SG#\24\24.
Figure 4-32. Voltage Protection Screen, 24 Tab
4-38
BE1-CDS240 Protection and Control
9365200990 Rev F
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......