replaces the values and time stamps stored in
Yesterday's Peak
registers with the values and time
stamps from
Today's Peak
registers. It then starts recording new information in
Today's Peak
registers.
The demand registers are stored in volatile memory.
The
Today's Peak
and
Yesterday's Peak
registers are read only. The values in the
Peak Since Reset
registers can be reset to zero or preset to a predetermined value. For example, if you are going to switch
some loads to take a feeder out of service and you do not want the abnormal loading to affect the values
stored in the
Peak Since Reset
registers. You may read these values prior to doing the switching and
then reset the registers to these values after the abnormal loading condition has passed.
Setting the Demand Reporting Function
For the demand reporting function to calculate demand, it is necessary to specify the demand interval,
calculation method, and which CT to monitor. This is done using BESTCOMS. Figure 6-3 illustrates the
BESTCOMS screen used to select demand-reporting settings. To open the screen shown in Figure 6-3,
select
Reporting and Alarms,
from the
Screens
pull-down menu. Then select the
I Demand
tab.
Alternately, setting may be made using the SG-DI (Read/Program Demand Current settings) and SG-DC
(Read/Set Demand Circuit) ASCII commands or the HMI using Screen 6.4.1, \SETUP\DMD\DETAILS.
Demand settings for include columns labeled
Phase, Neutral
, and
Neg.-Sequence
. Each of these
columns has settings for
Interval (Minutes), Calculation Method,
and
Current Threshold
.
Current
Threshold
display units are selectable from a pull-down menu allowing the selection of
Sec. Amps, Pri.
Amps, Per U Amps,
or
% Amps
. The default display unit is
Sec. Amps
.
Calculation Method
can be
Thermal, Block,
or
Sliding Block. Interval (Minutes)
can be set from 0 to 60.
Additionally,
Current Threshold
can be set on Demand Circuits 1 through 6. Choose the demand circuit
from the
Demand Circuits
pull-down menu.
Using the pull-down menus and buttons, make the application appropriate current demand settings.
Demand reporting settings are summarized in Table 6-4.
Figure 6-3. Reporting and Alarms Screen, I Demand Tab
6-8
BE1-CDS240 Reporting and Alarm Functions
9365200990 Rev F
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......