Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
20.08 TorqMinSPC (minimum torque speed controller)
Minimum torque limit - in percent of MotNomTorque (4.23) - at the output of the speed controller.
−
TorqRef2 (2.09)
Notes:
−
The used torque limit depends also on the converter's actual limitation situation (e.g. other torque limits,
current limits, field weakening). The limit with the largest value is valid.
−
Do not change the default setting of TorqMinSPC (20.08) for 2-Q drives, because M1CurLimBrdg2 (20.13)
is internally set to 0 % if QuadrantType (4.15) = BlockBridge2 (2-Q drive).
Int. Scaling: 100 == 1 % Type: SI
Volatile:
N
-325
0
-325%
%
20.09 TorqMaxTref (maximum torque of torque reference A/B)
Maximum torque limit - in percent of MotNomTorque (4.23) - for external references:
−
TorqRefA (25.01)
−
TorqRefB (25.04)
Note:
The used torque limit depends also on the converter's actual limitation situation (e.g. other torque limits,
current limits, field weakening). The limit with the smallest value is valid.
Int. Scaling: 100 == 1 % Type: SI
Volatile:
N
0.
325
325
%
20.10 TorqMinTref (minimum torque of torque reference A/B)
Minimum torque limit - in percent of MotNomTorque (4.23) - for external references:
−
TorqRefA (25.01)
−
TorqRefB (25.04)
Note:
The used torque limit depends also on the converter's actual limitation situation (e.g. other torque limits,
current limits, field weakening). The limit with the largest value is valid.
Int. Scaling: 100 == 1 % Type: SI
Volatile:
N
-325
0
-325
%
20.11 Unused
20.12 M1CurLimBrdg1 (current limit of bridge 1)
Current limit bridge 1 in percent of M1NomCur (99.03).
Notes:
−
Setting M1CurLimBrdg1 (20.12) to 0 % disables bridge 1.
−
The used current limit depends also on the converter's actual limitation situation (e.g. torque limits, other
current limits, field weakening). The limit with the smallest value is valid.
Int. Scaling: 100 == 1 % Type: SI
Volatile:
N
0
325
100
%
20.13 M1CurLimBrdg2 (current limit of bridge 2)
Current limit bridge 2 in percent of M1NomCur (99.03).
Notes:
−
Setting M1CurLimBrdg2 (20.13) to 0 % disables bridge 2.
−
The used current limit depends also on the converter's actual limitation situation (e.g. torque limits, other
current limits, field weakening). The limit with the largest value is valid.
−
M1CurLimBrdg2 (20.13) is internally set to 0 % if QuadrantType (4.15) = BlockBridge2 (2-Q drive). Thus,
do not change the default setting for 2-Q drives.
Int. Scaling: 100 == 1 % Type: SI
Volatile:
N
-325
0
-100
%
20.14 ArmAlphaMax (maximum firing angle)
Maximum firing angle (
α
) in degrees.
The maximum firing angle can be forced using AuxCtrlWord2 (7.03) bit 7.
Int. Scaling: 1 == 1 deg
Type: SI
Volatile:
N
0
165
150
deg
20.15 ArmAlphaMin (minimum firing angle)
Minimum firing angle (
α
) in degrees.
Int. Scaling: 1 == 1 deg
Type: SI
Volatile:
N
0
165
15
deg
20.16 - 20.17 Unused
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...