Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
15.09 FilterAO2 (filter analog output 2)
Analog output 2 filter time.
Int. Scaling: 1 == 1 ms
Type: I
Volatile:
N
0
10000
0
ms
15.10 ScaleAO2 (scaling analog output 2)
100 % of the signal/parameter selected with IndexAO2 (15.06) is scaled to the voltage in ScaleAO2 (15.10).
Int. Scaling: 1 == 1 mV
Type: I
Volatile:
N
0
10000
10000
mV
15.11 IndexAO3 (analog output 3 index)
Analog output 3 is controlled by a source (signal/parameter) selected with IndexAO3 (15.11). The format is -
xxyy, with: - = negate analog output, xx = group and yy = index.
Int. Scaling: 1 == 1
Type: SI
Volatile:
N
-9999
9999
-
-
15.12 CtrlWordAO3 (control word analog output 3
Analog output 3 can be written to via CtrlWordAO3 (15.12) using AP or overriding control if IndexAO3 (15.11)
is set to zero. Further description see group 19 Data Storage.
Int. Scaling: 1 == 1
Type: SI
Volatile:
Y
-32768
32767
0
-
15.13 ConvModeAO3 (convert mode analog output 3)
Analog output 3 signal offset:
0 = 0mA-20mA Uni 0 mA to 20 mA unipolar output
1 = 4mA-20mA Uni 4 mA to 20 mA unipolar output, default
2 = 10mA Offset
10 mA offset in the range 0 mA to 20 mA for testing or indication of bipolar signals (e.g.
torque, speed, etc.)
3 = 12mA Offset
12 mA offset in the range 4 mA to 20 mA for testing or indication of bipolar signals (e.g.
torque, speed, etc.)
4 = 0mA-20mA Abs absolute 0 mA to 20 mA unipolar output (negative values are shown positive)
Int. Scaling: 1 == 1
Type: C
Volatile:
N
4m
A
-20
m
A
U
ni
0m
A
-2
0m
A
A
bs
4m
A
-20
m
A
U
ni
-
15.14 FilterAO3 (filter analog output 3)
Analog output 3 filter time.
Int. Scaling: 1 == 1 ms
Type: I
Volatile:
N
0
10000
0
ms
15.15 ScaleAO3 (scaling analog output 3)
100 % of the signal/parameter selected with IndexAO3 (15.11) is scaled to the current in ScaleAO3 (15.15).
Int. Scaling: 1 == 1
Type: I
Volatile:
N
0
20
20
mA
15.16 IndexAO4 (analog output 4 index)
Analog output 4 is controlled by a source (signal/parameter) selected with IndexAO4 (15.16). The format is -
xxyy, with: - = negate analog output, xx = group and yy = index.
Int. Scaling: 1 == 1
Type: SI
Volatile:
N
-9999
9999
15.17 CtrlWordAO4 (control word analog output 4)
Analog output 4 can be written to via CtrlWordAO4 (15.17) using AP or overriding control if IndexAO4 (15.17)
is set to zero. Further description see group 19 Data Storage.
Int. Scaling: 1 == 1
Type: SI
Volatile:
Y
-32768
32767
0
-
15.18 ConvModeAO4 (convert mode analog output 4)
Analog output 4 signal offset:
0 = 0mA-20mA Uni 0 mA to 20 mA unipolar output
1 = 4mA-20mA Uni 4 mA to 20 mA unipolar output, default
2 = 10mA Offset
10 mA offset in the range 0 mA to 20 mA for testing or indication of bipolar signals (e.g.
torque, speed, etc.)
3 = 12mA Offset
12 mA offset in the range 4 mA to 20 mA for testing or indication of bipolar signals (e.g.
torque, speed, etc.)
4 = 0mA-20mA Abs absolute 0 mA to 20 mA unipolar output (negative values are shown positive)
Int. Scaling: 1 == 1
Type: C
Volatile:
N
4m
A
-20
m
A
U
ni
0m
A
-2
0m
A
A
bs
4m
A
-20
m
A
U
ni
-
15.19 FilterAO4 (filter analog output 4)
Analog output 4 filter time.
Int. Scaling: 1 == 1 ms
Type: I
Volatile:
N
0
10000
0
ms
15.20 ScaleAO4 (scaling analog output 4)
100 % of the signal/parameter selected with IndexAO4 (15.16) is scaled to the current in ScaleAO4 (15.20).
Int. Scaling: 1 == 1
Type: I
Volatile:
N
0
20
20
mA
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...