171
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
0
actual motor speed is out of the zero speed limit
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B12
EMFSpeed
1
M1SpeedFbSel (50.03) = EMF
0
no action
B13
FaultOrAlarm
1
fault or alarm indication
0
no fault or alarm indication
B14
DriveDirectionNeg 1
negative drive direction active - controlled by bit 8 of AuxCtrlWord2 (7.03)
0
positive drive direction active - controlled by bit 8 of AuxCtrlWord2 (7.03)
B15
AutoReclosing
1
auto reclosing logic is active
0
no action
Int. Scaling: 1 == 1
Type: I
Volatile:
Y
8.03 LimWord (limit word, LW)
Limit word:
Bit
active limit
B0
TorqMax (20.05) or TorqMaxAll (2.19)
B1
TorqMin (20.06) or TorqMinAll (2.20)
B2
TorqMaxSPC (20.07) or TorqMaxAll (2.19)
B3
TorqMinSPC (20.08) or TorqMinAll (2.20)
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B4
IndepTorqMaxSPC (20.24)
B5
IndepTorqMinSPC (20.25)
B6
TorqMaxTref (20.09)
B7
TorqMinTref (20.10)
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B8
M1SpeedMax (20.02)
B9
M1SpeedMin (20.01)
B10
M1CurLimBrdg1 (20.12)
B11
M1CurLimBrdg2 (20.13)
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B12-15
reserved
Int. Scaling: 1 == 1
Type: I
Volatile:
Y
8.04 Unused
8.05 DI StatWord (digital inputs status word, DISW)
Digital input word, shows the value of the digital inputs before inversion [DI1Invert (10.25), …, DI11Invert (10.35)]:
Bit
Name Comment / default setting
B0
DI1
ConvFanAck (10.20), actual setting depends on macro
B1
DI2
MotFanAck (10.06), actual setting depends on macro
B2
DI3
MainContAck (10.21), actual setting depends on macro
B3
DI4
Off2 (10.08), actual setting depends on macro
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B4
DI5
E Stop (10.09), actual setting depends on macro
B5
DI6
Reset (10.03), actual setting depends on macro
B6
DI7
OnOff (10.15), actual setting depends on macro
B7
DI8
StartStop (10.16), actual setting depends on macro
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B8
DI9
DI1 of the extension IO defined by DIO ExtModule1 (98.03)
B9
DI10 DI2 of the extension IO defined by DIO ExtModule1 (98.03)
B10
DI11 DI3 of the extension IO defined by DIO ExtModule1 (98.03)
B11
DI12 DI1 of the extension IO defined by DIO ExtModule2 (98.04). Only available for AP or overriding control.
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B12
DI13 DI2 of the extension IO defined by DIO ExtModule2 (98.04). Only available for AP or overriding control.
B13
DI14 DI3 of the extension IO defined by DIO ExtModule2 (98.04). Only available for AP or overriding control.
B14-15
reserved
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...