4.17 MaxBridgeTemp (maximum bridge temperature)
Maximum bridge temperature in degree centigrade. Read from TypeCode (97.01) or set with S MaxBrdgTemp
(97.04):
−
Read from TypeCode (97.01) if S MaxBrdgTemp (97.04) = 0
−
Read from S MaxBrdgTemp (97.04) if S MaxBrdgTemp (97.04)
≠
0
The drive trips with F504 ConvOverTemp [FaultWord1 (9.01) bit 3], when MaxBridgeTemp (4.17) is reached.
A104 ConvOverTemp [AlarmWord1 (9.06) bit 3] is set, when the actual converter temperature is
approximately 5°C below MaxBridgeTemp (4.17).
Int. Scaling: 1 == 1 °C
Type: I
Volatile:
Y
-
-
-
°C
4.18 - 4.19 Unused
4.20 Ext IO Stat (external IO status)
Status of external I/O:
Bit
Value Comment
B0
1
RAIO-xx detected, see AIO ExtModule (98.06)
0
RAIO-xx not existing or faulty
B1-B3
reserved
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B4
1
first RDIO-xx detected, see DIO ExtModule1 (98.03)
0
first RDIO-xx not existing or faulty
B5
1
second RDIO-xx detected, see DIO ExtModule2 (98.04)
0
second RDIO-xx not existing or faulty
B6-B7
reserved
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B8-B11
reserved
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B12
reserved
B13
1
SDCS-COM-8 detected
0
SDCS-COM-8 faulty
B14 - B15
reserved
Int. Scaling: 1 == 1
Type: C
Volatile:
Y
4.21 CPU Load (load of processor)
The calculating power of the processor is divided into two parts:
−
CPU Load (4.21) shows the load of the firmware and
−
ApplLoad (4.22) shows the load of AP and the winder macro.
Neither should reach 100%.
Int. Scaling: 10 == 1 %
Type: I
Volatile:
Y
-
-
-
%
4.22 ApplLoad (load of application)
The calculating power of the processor is divided into two parts:
−
CPU Load (4.21) shows the load of the firmware and
−
ApplLoad (4.22) shows the load of AP and the winder macro.
Neither should reach 100%.
Int. Scaling: 10 == 1 %
Type: I
Volatile:
Y
-
-
-
%
4.23 MotTorqNom (motor nominal torque)
Calculated nominal motor torque:
[
]
)
04
.
99
(
1
)
03
.
99
(
1
*
)
10
.
43
(
1
*
)
03
.
99
(
1
)
02
.
99
(
1
*
*
2
60
)
23
.
4
(
BaseSpeed
M
NomCur
M
ArmR
M
MotCur
M
NomVolt
M
MotTorqNom
−
=
π
Int. Scaling: 1 == 1 Nm
Type: I
Volatile:
Y
-
-
-
Nm
4.24 ProgressSignal (progress signal for auto tunings)
Progress signal for auto tunings used for Startup Assistants.
Int. Scaling: 1 == 1 %
Type: I
Volatile:
Y
-
-
-
%
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...