103
Communication
3ADW000379R0501 DCS550 Manual e e
DsetXplus1Val2 (92.02)
104, default
MotSpeed (1.04);
input data word 2 (speed actual) 2
nd
data word from drive
to overriding control
(40005 <= data word 2.2)
DsetXplus1Val3 (92.03)
209, default
TorqRef2 (2.09);
input data word 3 (torque reference) 3
rd
data word from
drive to overriding control
(40006 <= data word 2.3)
up to, …,
DsetXplus7Val1 (92.10)
904, default
Faultword4 (9.04);
input data word 10 (fault word 4) 10
th
data word from drive
to overriding control
(40022 <= data word 8.1)
Notes:
−
New settings of group 52 take effect only after the next power up of the adapter.
−
±
20,000 speed units (decimal) for speed reference [SpeedRef (23.01)] and speed actual [MotSpeed
(1.04)] corresponds to the speed shown in SpeedScaleAct (2.29).
Setting of PLC, parameter groups 90 and 92
Setting of PLC, parameter groups 90 and 92 depending on desired data words
Switch on sequence
Please see the example at the end of this chapter.