Fault tracing
3ADW000379R0501 DCS550 Manual e e
7-segment
display
Text on DCS
Control Panel
and DWL
Definition / Action
Alarm-
word
Alarm is
active when
A
lar
m
level
usually slower than the one of the drive). Check:
−
ComLossCtrl (30.28), FB TimeOut (30.35),
CommModule (98.02)
−
parameter settings of group 51 (fieldbus)
−
fieldbus cable
−
fieldbus termination
−
fieldbus adapter
A129 129 ParRestored Parameter restored:
The parameters found in the flash were invalid at power-
up (checksum fault). All parameters were restored from
the parameter backup.
9.07,
bit 12
always
4
A130 130
LocalCmdLoss
Local command loss:
Connection fault with DCS Control Panel or DWL. Check:
−
LocalLossCtrl (30.27)
−
if control DCS Control Panel is disconnected
−
connection adapter
−
cables
9.07,
bit 13
local
4
A131 131 ParAdded
Parameter added:
A new firmware with a different amount of parameters was
downloaded. The new parameters are set to their default
values. The parameters causing the alarm can be
identified in Diagnosis (9.11). Check:
−
new parameters and set them to the desired values
9.07,
bit 14
after
download of
firmware for
max. 10 s
4
A132 132 ParConflict
Parameter setting conflict:
Is triggered by parameter settings conflicting with other
parameters. The parameters causing the alarm can be
identified in Diagnosis (9.11).
9.07,
bit 15
always
4
A133 133 RetainInv
Retain data invalid:
Set when the retain data in the flash are invalid during
power-up. In this case, the backup data are used.
Note:
The backup of the lost retain data reflects the status at the
previous power-up.
Examples for retain data are:
−
fault logger data,
−
Data1 (19.01) to Data4 (19.04) and
−
I/O options (see group 98)
The situation of invalid retain data occurs, if the auxiliary
voltage of the DCS550 is switched off about 2 seconds
after power-up (while the retain data sector is being
rearranged). Check:
−
if the flash of the SDCS-CON-F is defective and
−
if the auxiliary power supply has a problem
9.08,
bit 0
directly after
energizing of
electronics for
max. 10 s
4
A134 134 ParComp
Parameter compatibility:
When downloading parameter sets or during power-up the
firmware attempts to write the parameters. If the setting is
not possible or not compatible, the parameter is set to
default. The parameters causing the alarm can be
identified in Diagnosis (9.11). Check:
−
parameter setting
9.08,
bit 1
after
download of a
parameter set
for max. 10 s
4
A135 135
Parameter up- or download failed:
9.08,
after up- or
4
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...