Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal and parameter list
Chapter overview
This chapter describes all signals and parameters of the DCS550.
Signal groups list
Signals are measured and calculated actual values of the drive. This includes the control-, status-, limit-, fault-
and alarm words. The drive’s signals are available in groups 1 to 9. None of the values inside these groups is
stored in the flash and thus volatile.
Note:
Signals in group 7 can be written to by means of DWL, DCS Control Panel, AP or overriding control.
The following table gives an overview of all signal groups:
Group
Description
1
2
3
4
5
6
7
8
9
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
1.08 MotTorq (motor torque)
Motor torque in percent of MotNomTorque (4.23):
−
Filtered by means of a 6th order FIR filter (sliding average filter), filter time is 1 mains voltage period.
Int. Scaling: 100 == 1 % Type: SI
Volatile:
Y
-
-
-
%
2.17 SpeedRefUsed (used speed reference)
Used speed reference selected with:
−
Ref1Mux (11.02) and Ref1Sel (11.03) or
−
Ref2Mux (11.12) and Ref2Sel (11.06)
Int. Scaling: (2.29)
Type: SI
Volatile:
Y
-
-
-
rp
m
Sample of signals
All signals are read-only. However, the overriding control can write to the control words, but it only affects the
RAM.
Min., max., def.:
Minimum, maximum and default values are not valid for groups 1 to 9.
Unit:
Shows the physical unit of a signal, if applicable. The unit is displayed in the DCS Control Panel and DWL.
Group.Index:
Signal and parameter numbers consists of group number and its index.
Integer Scaling:
Communication between the drive and the overriding control uses 16-bit integer values. The overriding control
has to use the information given in integer scaling to read the value of the signal properly.
Example1:
If the overriding control reads MotTorq (1.08) 100 corresponds to 1 % torque.
Example2:
If the overriding control reads SpeedRefUsed (2.17) 20,000 equals the speed (in rpm) shown in
SpeedScaleAct (2.29).
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...