Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B12
reserved
B13
1
current controller not released, because DevLimPLL (97.13) is reached
0
no action
B14
1
mains not in synchronism (AC), F514 MainsNotSync [FaultWord1 (9.01) bit 13]
0
no action
B15
1
Current controller not released.
0
no action
Note:
A set bit does not necessarily lead to a fault message it depends also on the status of the drive.
Int. Scaling: 1 == 1
Type: I
Volatile:
Y
6.05 SelBridge (selected bridge)
Selected (current-conducting) bridge:
0 = NoBridge no bridge selected
1 = Bridge1 bridge 1 selected (motoring bridge)
2 = Bridge2 bridge 2 selected (generating bridge)
Int. Scaling: 1 == 1
Type: C
Volatile:
Y
-
-
-
-
Group 7: Control words
It is possible to write on all signals in this group - except UsedMCW (7.04) - my means of DWL, DCS Control
Panel, AP or overriding control.
7.01 MainCtrlWord (main control word, MCW)
The main control word contains all drive depending commands and can be written to by AP or overriding control:
Bit
Name
Value Comment
B0
On (Off1N)
1
Command to RdyRun state.
With MainContCtrlMode (21.16) = On: Closes contactors, starts field exciter and fans.
With MainContCtrlMode (21.16) = On&Run:
RdyRun flag in MainStatWord (8.01) is forced to 1
0
Command to Off state. Stopping via Off1Mode (21.02).
B1
Off2N
1
No Off2 (Emergency Off / Coast Stop)
0
Command to OnInhibit state. Stop by coasting. The firing pulses are immediately set to 150
degrees to decrease the armature current. When the armature current is zero the firing pulses
are blocked, the contactors are opened, field exciter and fans are stopped.
Off2N has priority over OffN3 and On.
B2
Off3N
1
No Off3 (E-stop)
0
Command to OnInhibit state. Stopping via E StopMode (21.04).
Off3N has priority over On.
B3
Run
1
Command to RdyRef state. The firing pulses are released and the drive is running with the
selected speed reference.
0
Command to RdyRun state. Stop via StopMode (21.03).
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B4
RampOutZero
1
no action
0
speed ramp output is forced to zero
B5
RampHold
1
no action
0
freeze (hold) speed ramp
B6
RampInZero 1
no action
0
speed ramp input is forced to zero
B7
Reset
1
acknowledge fault indications with the positive edge
0
no action
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B8
Inching1
1
constant speed defined by FixedSpeed1 (23.02), active only with CommandSel (10.01) =
MainCtrlWord and RampOutZero = RampHold = RampInZero = 0; Inching2 overrides
Inching1 alternatively Jog1 (10.17) can be used
0
no action
B9
Inching2
1
constant speed defined by FixedSpeed2 (23.03), active only with CommandSel (10.01) =
MainCtrlWord and RampOutZero = RampHold = RampInZero = 0; Inching2 overrides
Inching1 alternatively Jog2 (10.18) can be used
0
no action
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...