Communication
3ADW000379R0501 DCS550 Manual e e
IP address setting from following parameters
IP address 1 (51.04)
192**
e.g. IP address:
192.168.0.1
IP address 2 (51.05)
168**
IP address 3 (51.06)
0**
IP address 4 (51.07)
1**
Subnet mask 1 (51.08)
255
e.g. subnet mask:
255.255.255.0
Subnet mask 2 (51.09)
255
Subnet mask 3 (51.10)
255
Subnet mask 4 (51.11)
0
GW address 1 (51.12)
0
e.g. gateway address:
0.0.0.0
GW address 2 (51.13)
0
GW address 3 (51.14)
0
GW address 4 (51.15)
0
Protocol (51.16)
2
1 = Ethernet/IP AC/DC communication profile
2 = Ethernet/IP ABB Drives communication profile
Modbus timeout (51.17)
22
0 = no monitoring
1 = 100 ms
22 = 2200 ms
Stop function (51.18)
0
0 = Ramp stop
Output 1 (51.19)
1
data word 1; setting via parameter 90.01
Output 2 (51.20)
2
data word 2; setting via parameter 90.02
Output 3 (51.21)
3
data word 3; setting via parameter 90.03
Output 4 (51.22)
7
data word 4; setting via parameter 90.04
Input 1 (51.23)
4
data word 1; setting via parameter 92.01
Input 2 (51.24)
5
data word 2; setting via parameter 92.02
Input 3 (51.25)
6
data word 3; setting via parameter 92.03
Input 4 (51.26)
10
data word 4; setting via parameter 92.04
FBA PAR REFRESH (51.27)
DONE, default
If a fieldbus parameter is changed its new value takes
effect only upon setting FBA PAR REFRESH (51.27) =
RESET or at the next power up of the fieldbus adapter.
* Read-only or automatically detected by Ethernet adapter
** If all DIP switches (S1) are OFF; the IP address is set according to parameters 51.04, …, 51.07. In case at
least one DIP switch is on, the last byte of the IP address [IP address 4 (51.07)] is set according to the DIP
switches (see page 42).
Note:
±
20,000 speed units (decimal) for speed reference [SpeedRef (23.01)] and speed actual [MotSpeed (1.04)]
corresponds to the speed shown in SpeedScaleAct (2.29).
Up to 4 data words
The content of Input/Output 1 to 4 can be configured with the RETA-01 configuration parameters. Please see
table RETA-01 Ethernet/IP configuration parameters, which contains all the necessary basic settings.
Up to 10 data words
The DCS550 supports up to 10 data words in each direction. The first configuration of the RETA-01 adapter
has to be done according to the table RETA-01 Ethernet/IP configuration parameters, which contains all the
necessary basic settings.
The additional desired data words have to be configured via the fieldbus network using Vendor Specific Drive
I/O Object (Class 91h). The adapter will automatically save the configuration.
The table RETA-01 Ethernet/IP configuration parameters shows the index configuration numbers and the
corresponding data words (via data sets).
Please note: The grayed index is also addressed via group 51, please set the outputs and inputs to the same
configuration numbers as shown in the table RETA-01 Ethernet/IP configuration parameters.
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...