105
Communication
3ADW000379R0501 DCS550 Manual e e
GW address 1 (51.12)
0
e.g. gateway address:
0.0.0.0
GW address 2 (51.13)
0
GW address 3 (51.14)
0
GW address 4 (51.15)
0
Protocol (51.16)
0
0 = Modbus/TCP
Modbus timeout (51.17)
22
0 = no monitoring
1 = 100 ms
22 = 2200 ms
Stop function (51.18)
NA
not applicable when using Modbus/TCP
Output 1 (51.19)
1
data word 1; setting via parameter 90.01
Output 2 (51.20)
2
data word 2; setting via parameter 90.02
Output 3 (51.21)
3
data word 3; setting via parameter 90.03
Output 4 (51.22)
7
data word 4; setting via parameter 90.04
Input 1 (51.23)
4
data word 1; setting via parameter 92.01
Input 2 (51.24)
5
data word 2; setting via parameter 92.02
Input 3 (51.25)
6
data word 3; setting via parameter 92.03
Input 4 (51.26)
10
data word 4; setting via parameter 92.04
FBA PAR REFRESH (51.27)
DONE, default
If a fieldbus parameter is changed its new value takes
effect only upon setting FBA PAR REFRESH (51.27) =
RESET or at the next power up of the fieldbus adapter.
* Read-only or automatically detected by Ethernet adapter
** If all DIP switches (S1) are OFF; the IP address is set according to parameters 51.04, …, 51.07. In case at
least one DIP switch is on, the last byte of the IP address [IP address 4 (51.07)] is set according to the DIP
switches (see page 42).
Note:
±
20,000 speed units (decimal) for speed reference [SpeedRef (23.01)] and speed actual [MotSpeed (1.04)]
corresponds to the speed shown in SpeedScaleAct (2.29).
Switch on sequence
Please see the example at the end of this chapter.
Profibus communication with fieldbus adapter RPBA-01
General
This chapter gives additional information using the Profibus adapter RPBA-01 together with the DCS550.
RPBA-01 - DCS550
The Profibus communication with the drive requires the option RPBA-01.
Related documentation
User’s Manual PROFIBUS DP Adapter Module RPBA-01. The quoted page numbers correspond to the User’s
Manual.
Overriding control configuration
Supported operation mode is VENDOR SPECIFIC for ABB Drives (see page 19 and 20). The RPBA-01 uses
data consistent communication, meaning that the whole data frame is transmitted during a single program
cycle. Some overriding controls handle this internally, but others must be programmed to transmit data
consistent telegrams.
Mechanical and electrical installation
If not already done so insert RPBA-01 into slot 1 of the drive (see page 21).
Drive configuration
Activate the Profibus adapter by means of CommModule (98.02) (see page 22). Please note that the DCS550
works only with the ABB Drives profile.
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...