160
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
2.22 TorqUsedMax (used torque maximum)
Relative positive torque limit in percent of MotNomTorque (4.23). Selected with:
−
TorqUsedMaxSel (20.18)
Connected to torque limiter after TorqRef4 (2.11).
Int. Scaling: 100 == 1 % Type: SI
Volatile:
Y
-
-
-
%
2.23 TorqUsedMin (used torque minimum)
Relative negative torque limit in percent of MotNomTorque (4.23). Selected with:
−
TorqUsedMinSel (20.19)
Connected to torque limiter after TorqRef4 (2.11).
Int. Scaling: 100 == 1 % Type: SI
Volatile:
Y
-
-
-
%
2.24 TorqRefExt (external torque reference)
Relative external torque reference value in percent of MotNomTorque (4.23) after torque reference A selector:
−
TorqRefA (25.01) and
−
TorqRefA Sel (25.10)
Int. Scaling: 100 == 1 % Type: SI
Volatile:
Y
-
-
-
%
2.25 Unused
2.26 TorqLimAct (actual used torque limit)
Shows parameter number of the actual active torque limit:
0 = 0
no limitation active
1 = 2.19
TorqMaxAll (2.19) is active, includes current limits and field weakening
2 = 2.20
TorqMinAll (2.20) is active, includes current limits and field weakening
3 = 2.22
TorqUsedMax (2.22) selected torque limit is active
4 = 2.23
TorqUsedMin (2.23) selected torque limit is active
5 = 20.07
TorqMaxSPC (20.07) speed controller limit is active
6 = 20.08
TorqMinSPC (20.08) speed controller limit is active
7 = 20.09
TorqMaxTref (20.09) external reference limit is active
8 = 20.10
TorqMinTref (20.10) external reference limit is active
9 = 20.22
TorqGenMax (20.22) regenerating limit is active
10 = 20.24
IndepTorqMaxSPC (20.24) independent speed controller limit is active
11 = 20.25
IndepTorqMinSPC (20.25) independent speed controller limit is active
12 = 2.08
TorqRef1 (2.08) limits TorqRef2 (2.09), see also TorqSel (26.01)
Int. Scaling: 1 == 1
Type: C
Volatile:
Y
-
-
-
-
2.27 - 2.28 Unused
2.29 SpeedScaleAct (actual used speed scaling)
The value of SpeedScaleAct (2.29) equals 20,000 internal speed units. Thus follows 20,000 speed units ==
M1SpeedScale (50.01), in case M1SpeedScale (50.01)
≥
10 or 20,000 speed units == maximum absolute
value of M1SpeedMin (20.01) and M1SpeedMax (20.02), in case M1SpeedScale (50.01) < 10.
Mathematically speaking:
If (50.01)
≥
10 then 20,000 == (50.01) in rpm
If (50.01) < 10 then 20,000 == Max [|(20.01)|, |(20.02)|] in rpm
Int. Scaling: 1 == 1 rpm
Type: SI
Volatile:
Y
-
-
-
rp
m
2.30 SpeedRefExt1 (external speed reference 1)
External speed reference 1 after reference 1 multiplexer:
−
Ref1Mux (11.02)
Int. Scaling: (2.29)
Type: SI
Volatile:
Y
-
-
-
rp
m
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...