Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
84.04 Block1Type (function block 1 type)
Selects the type for function block 1 [Block Parameter Set 1 (BPS1)]. Detailed description of the type can be
found in chapter ‘
0 = NotUsed
function block is not used
1 = ABS
absolute value
2 = ADD
sum
3 = AND
AND
4 = Bitwise
bit compare
5 = Bset
bit set
6 = Compare
compare
7 = Count
counter
8 = D-Pot
ramp
9 = Event
event
10 = Filter
filter
11 = Limit
limit
12 = MaskSet
mask set
13 = Max
maximum
14 = Min
minimum
15 = MulDiv
multiplication and division
16 = OR
OR
17 = ParRead
parameter read
18 = ParWrite
parameter write
19 = PI
PI-controller
20 = PI-Bal
initialization for PI-controller
21 = Ramp
ramp
22 = SqWav
square wave
23 = SR
SR flip-flop
24 = Switch-B
switch Boolean
25 = Switch-I
switch integer
26 = TOFF
timer off
27 = TON
timer on
28 = Trigg
trigger
29 = XOR
exclusive OR
30 = Sqrt
square root
Int. Scaling: 1 == 1
Type: C
Volatile:
N
No
tUs
e
d
Sq
rt
No
tUs
e
d
-
84.05 Block1In1 (function block 1 input 1)
Selects the source for input 1 of function block 1 (BPS1). There are 2 types of inputs, signals/parameters and
constants:
−
Signals/parameters are all signals and parameters available in the drive. The format is -xxyy, with: - =
negate signal/parameter, xx = group and yy = index.
Example:
To connect negated SpeedRef (23.01) set Block1In1 (84.05) = -2301 and Block1Attrib (84.08) = 0h.
To get only a certain bit e.g. RdyRef bit 3 of MainStatWord (8.01) set Block1In1 (84.05) = 801 and
Block1Attrib (84.08) = 3h.
−
Constants are feed directly into the function block input. Declare them by means of Block1Attrib (84.08).
Example:
To connect the constant value of 12345 set Block1In1 (84.05) = 12345 and Block1Attrib (84.08) = 1000h.
Int. Scaling: 1 == 1
Type: SI
Volatile:
N
-32768
32767
0
-
84.06 Block1In2 (function block 1 input 2)
Selects the source for input 2 of function block 1 (BPS1). Description see Block1In1 (84.05), except:
To get only a certain bit e.g. RdyRef bit 3 of MainStatWord (8.01) set Block1In2 (84.06) = 801 and
Block1Attrib (84.08) = 30h.
Int. Scaling: 1 == 1
Type: SI
Volatile:
N
-32768
32767
0
-
84.07 Block1In3 (function block 1 input 3)
Selects the source for input 3 of function block 1 (BPS1). Description see Block1In1 (84.05), except:
To get only a certain bit e.g. RdyRef bit 3 of MainStatWord (8.01) set Block1In3 (84.07) = 801 and
Block1Attrib (84.08) = 300h.
Int. Scaling: 1 == 1
Type: SI
Volatile:
N
-32768
32767
0
-
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...