220
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
30.29 AI Mon4mA (analog input 4 mA fault selector)
AI Mon4mA (30.29) determines the reaction to an undershoot of one of the analog inputs under 4 mA / 2 V - if
it is configured to this mode:
0 = NotUsed
1 = Fault
the drive stops according to FaultStopMode (30.30) and trips with F551 AIRange
[FaultWord4 (9.04) bit 2], default
2 = LastSpeed
the drive continues to run at the last speed and sets A127 AIRange [AlarmWord2 (9.07)
bit 10]
3 = FixedSpeed1
the drive continues to run with FixedSpeed1 (23.02) and sets A127 AIRange
[AlarmWord2 (9.07) bit 10]
Int. Scaling: 1 == 1
Type: C
Volatile:
N
No
tUs
e
d
F
ix
e
dS
pee
d1
F
aul
t
-
30.30 FaultStopMode (fault stop mode)
FaultStopMode (30.30) determines the reaction to a fault of trip level 4:
0 = RampStop
The input of the drives ramp is set to zero. Thus, the drive stops according to E
StopRamp (22.04). When reaching M1ZeroSpeedLim (20.03) the firing pulses are set to
150 degrees to decrease the armature current. When the armature current is zero the
firing pulses are blocked, the contactors are opened, field exciter and fans are stopped.
1 = TorqueLimit
The output of the drives ramp is set to zero. Thus, the drive stops at the active torque
limit. When reaching M1ZeroSpeedLim (20.03) the firing pulses are set to 150 degrees
to decrease the armature current. When the armature current is zero the firing pulses are
blocked, the contactors are opened, field exciter and fans are stopped.
2 = CoastStop
The firing pulses are immediately set to 150 degrees to decrease the armature current.
When the armature current is zero the firing pulses are blocked, the contactors are
opened, field exciter and fans are stopped.
3 = DynBraking
dynamic braking
Note:
FaultStopMode (30.30) does not apply to communication faults.
Int. Scaling: 1 == 1
Type: C
Volatile:
N
R
am
pS
to
p
D
y
nB
rak
ing
R
am
pS
to
p
-
30.31 ExtFaultSel (external fault selector)
The drive trips with F526 ExternalDI [FaultWord2 (9.02) bit 9] if a binary input for an external fault is selected
and 1:
0 = NotUsed
default
1 = DI1
1 = fault, 0 = no fault
2 = DI2
1 = fault, 0 = no fault
3 = DI3
1 = fault, 0 = no fault
4 = DI4
1 = fault, 0 = no fault
5 = DI5
1 = fault, 0 = no fault
6 = DI6
1 = fault, 0 = no fault
7 = DI7
1 = fault, 0 = no fault
8 = DI8
1 = fault, 0 = no fault
9 = DI9
1 = fault, 0 = no fault, Only available with digital extension board
10 = DI10
1 = fault, 0 = no fault, Only available with digital extension board
11 = DI11
1 = fault, 0 = no fault, Only available with digital extension board
12 = MCW Bit11
1 = fault, 0 = no fault, MainCtrlWord (7.01) bit 11
13 = MCW Bit12
1 = fault, 0 = no fault, MainCtrlWord (7.01) bit 12
14 = MCW Bit13
1 = fault, 0 = no fault, MainCtrlWord (7.01) bit 13
15 = MCW Bit14
1 = fault, 0 = no fault, MainCtrlWord (7.01) bit 14
16 = MCW Bit15
1 = fault, 0 = no fault, MainCtrlWord (7.01) bit 15
Int. Scaling: 1 == 1
Type: C
Volatile:
N
No
tUs
e
d
M
C
W
B
it
15
No
tUs
e
d
-
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...