83.04 TimeLevSel (time level select)
Selects the cycle time for AP. This setting is valid for all function blocks.
0 = Off
no task selected
1 = 5ms
AP runs with 5 ms
2 = 20ms
AP runs with 20 ms
3 = 100ms
AP runs with 100 ms
4 = 500ms
AP runs with 500 ms
A136 NoAPTaskTime [AlarmWord3 (9.08) bit 3] is set when TimeLevSel (83.04) is not set to 5 ms, 20 ms,
100 ms or 500 ms but AdapProgCmd (83.01) is set to Start, SingleCycle or SingleStep.
Int. Scaling: 1 == 1
Type: C
Volatile:
N
Of
f
500m
s
Of
f
-
83.05 PassCode (pass code)
The pass code is a number between 1 and 65535 to write protect AP by means of EditCmd (83.02). After
using Protect or Unprotect PassCode (83.05) is automatically set back to zero.
Attention:
Do not forget the pass code!
Int. Scaling: 1 == 1
Type: I
Volatile:
Y
0
65535
0
-
83.06 BreakPoint (break point)
Breakpoint for AdapProgCmd (83.01) = SingleCycle.
The break point is not used, if BreakPoint (83.06) is set to zero.
Int. Scaling: 1 == 1
Type: I
Volatile:
Y
0
16
0
-
Group 84: AP
84.01 AdapPrgStat (AP status word)
AP status word:
Bit Name
Value Comment
B0 Bit 0
1
AP is running
0
AP is stopped
B1 Bit 1
1
AP can be edited
0
AP cannot be edited
B2 Bit 2
1
AP is being checked
0
no action
B3 Bit 3
1
AP is faulty
0
AP is OK
B4 Bit 4
1
AP is protected
0
AP is unprotected
Faults in AP can be:
−
used function block with not at least input 1 connection
−
used pointer is not valid
−
invalid bit number for function block Bset
−
location of function block PI-Bal after PI function block
Int. Scaling: 1 == 1
Type: I
Volatile:
Y
-
-
-
-
84.02 FaultedPar (faulted parameters)
AP will be checked before running. If there is a fault, AdapPrgStat (84.01) is set to “faulty” and FaultedPar
(84.02) shows the faulty input.
Note:
In case of a problem, check the value and the attribute of the faulty input.
Int. Scaling: 1 == 1
Type: I
Volatile:
Y
-
-
-
-
84.03 LocationCounter (location counter)
Location counter for AdapProgCmd (83.01) = SingleStep shows the function block number, which will be
executed next.
Int. Scaling: 1 == 1
Type: I
Volatile:
Y
-
-
-
-
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...