Fault tracing
3ADW000379R0501 DCS550 Manual e e
7-segment
display
Text on DCS
Control Panel
and DWL
Definition / Action
Alarm-
word
Alarm is
active when
A
lar
m
level
A101 101 Off2ViaDI
Off2 (Emergency Off / Coast stop) pending via digital
input - start inhibition:
There is no problem with the drive itself! Check:
−
Off2 (10.08), if necessary invert the signal (group 10)
9.06,
bit 0
RdyRun = 1 1
A102 102 Off3ViaDI
Off3 (E-stop) pending via digital input:
There is no problem with the drive itself! Check:
−
E Stop (10.09), if necessary invert the signal (group
10)
9.06,
bit 1
RdyRun = 1 1
A103 103 DC BreakAck DC-Breaker acknowledge missing:
α
is set to 150° and single firing pulses are given, thus the
drive cannot be started or re-started while the DC-breaker
acknowledge is missing. Check:
−
DC BreakAck (10.23), if necessary invert the signal
(group 10)
9.06,
bit 2
RdyRun = 1 3
A104 104
ConvOverTemp
Converter overtemperature:
Wait until the converter is cooled down. Shutdown
temperature see MaxBridgeTemp (4.17). The converter
overtemperature alarm will already appear at
approximately 5°C below the shutdown temperature.
Check:
−
FanDly (21.14)
−
converter cover missing
−
converter fan supply voltage
−
converter fan direction of rotation
−
converter fan components
−
converter cooling air inlet (e.g. filter)
−
converter cooling air outlet
−
ambient temperature
−
inadmissible load cycle
−
connector X12 on SDCS-CON-F
−
connector X12 and X22 on SDCS-PIN-F
−
if TypeCode (97.01) and S MaxBridgeTemp (97.04)
are set properly
9.06,
bit 3
always
2
A105 105 DynBrakeAck Dynamic braking is still pending:
α
is set to 150° and single firing pulses are given.
Check:
−
DynBrakeAck (10.22)
9.06,
bit 4
RdyRun = 1 3
A106 106 M1OverTemp Motor measured overtemperature:
Check:
−
M1AlarmLimTemp (31.06)
−
motor temperature
−
motor fan supply voltage
−
motor fan direction of rotation
−
motor fan components
−
motor cooling air inlet (e.g. filter)
−
motor cooling air outlet
−
motor temperature sensors and cabling
−
ambient temperature
−
inadmissible load cycle
−
inputs for temperature sensor on SDCS-CON-F
9.06,
bit 5
always
2
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...