268
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
99.07 ApplRestore (application restore)
Setting ApplRestore (99.07) = Yes starts the loading / storing of the macro (preset parameter set) selected by
means of ApplMacro (99.08). ApplRestore (99.07) is automatically set back to Done after the chosen action is
finished:
0 = Done
no action or macro change completed, default
1 = Yes
macro selected with ApplMacro (99.08) will be loaded into the drive
Notes:
−
Macro changes are only accepted in Off state [MainStatWord (8.01) bit 1 = 0].
−
It takes about 2 s, until the new parameter values are active.
Int. Scaling: 1 == 1
Type: C
Volatile:
Y
D
one
Ye
s
D
one
-
99.08 ApplMacro (application macro)
ApplMacro (99.08) selects the macro (preset parameter sets) to be loaded / stored into the RAM and flash. In
addition to the preset macros, two user-defined macros (User1 and User2) are available.
The operation selected by ApplMacro (99.08) is started immediately by setting ApplRestore (99.07) = Yes.
ApplMacro (99.08) is automatically set back to NotUsed after the chosen action is finished. The selected
macro is shown in MacroSel (8.10):
0 = NotUsed
default
1 = Factory
load macro factory (default parameter set) into RAM and flash - User1 and User2
will not be influenced
2 = User1Load
load macro User1 into RAM and flash
3 = User1Save
save actual parameter set form RAM into macro User1
4 = User2Load
load macro User2 into RAM and flash
5 = User2Save
save actual parameter set form RAM into macro User2
6 = Standard
load macro standard into RAM and flash
7 = Man/Const
load macro manual / constant speed into RAM and flash
8 = Hand/Auto
load macro hand (manual) / automatic into RAM and flash
9 = Hand/MotPot
load macro hand (manual) / motor potentiometer into RAM and flash
10 = reserved
11 = MotPot
load macro motor potentiometer into RAM and flash
12 = TorqCtrl
load macro torque control into RAM and flash
13 = TorqLimit
load macro torque limit into RAM and flash
14 = DemoStandard
load macro demo standard into RAM and flash
15 = 2WreDCcontUS
load macro 2 wire with US style DC-breaker into RAM and flash
16 = 3WreDCcontUS
load macro 3 wire with US style DC-breaker into RAM and flash
17 = 3WreStandard
load macro 3 wire standard into RAM and flash
Notes:
−
When loading a macro, group 99 is set / reset as well.
−
If User1 is active, AuxStatWord (8.02) bit 3 is set. If User2 is active, AuxStatWord (8.02) bit 4 is set.
−
It is possible to change all preset parameters of a loaded macro. On a macro change or an application
restore command of the actual macro the macro depending parameters are restored to the macro’s default
values.
−
In case macro User1 or User2 is loaded by means of ParChange (10.10), it is not saved into the flash and
thus not valid after the next power on.
Int. Scaling: 1 == 1
Type: C
Volatile:
Y
No
tUs
e
d
T
o
rq
C
trl
No
tUs
e
d
-
99.09 DeviceName (device name)
DeviceName (99.09) is fixed set to DCS550 and cannot be changed.
Note:
This parameter is only visible if a SDCS-COM-8 is connected.
Int. Scaling: 1 == 1
Type: C
Volatile:
N
DCS
5
50
DCS
5
5
0
DCS
5
5
0
-
99.10 NomMainsVolt (nominal AC mains voltage)
Nominal mains voltage (AC) of the supply. The default and maximum values are preset automatically
according to TypeCode (97.01).
Absolute max. is 525 V
Int. Scaling: 1 == 1 V
Type: I
Volatile:
N
0
(97.
01)
(97.
01)
V
99.11 M1NomFldCur (nominal field current)
Nominal field current from the motor rating plate.
Int. Scaling: 100 == 1 A
Type: I
Volatile:
N
0
.3
35
0
.3
A
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...