193
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
13.07 ConvModeAI2 (conversion mode analog input 2)
The distinction between voltage and current is done via jumpers on the SDCS-CON-F:
0 =
±
10V Bi
-10 V to 10 V / -20 mA to 20 mA bipolar input, default
1 = 0V-10V Uni
0 V to 10 V / 0 mA to 20 mA unipolar input
2 = 2V-10V Uni
2 V to 10 V / 4 mA to 20 mA unipolar input
3 = 5V Offset
5 V / 10 mA offset in the range 0 V to 10 V / 0 mA to 20 mA for testing or indication of
bipolar signals (e.g. torque, speed, etc.)
4 = 6V Offset
6 V / 12 mA offset in the range 2 V to 10 V / 4 mA to 20 mA for testing or indication of
bipolar signals (e.g. torque, speed, etc.)
Int. Scaling: 1 == 1
Type: C
Volatile:
N
±
1
0
V Bi
6
V
O
ffs
e
t
±
1
0
V Bi
-
13.08 FilterAI2 (filter time analog input 2)
Analog input 2 filter time. The hardware filter time is
≤
2ms.
Int. Scaling: 1 == 1 ms
Type: I
Volatile:
N
0
10000
0
ms
13.09 AI3HighVal (analog input 3 high value)
+100 % of the input signal connected to analog input 3 is scaled to the voltage in AI3HighVal (13.09).
Note:
Can only be used for voltage measurement.
Int. Scaling: 1 == 1 mV
Type: I
Volatile:
N
-10000
10000
10000
mV
13.10 AI3LowVal (analog input 3 low value)
-100 % of the input signal connected to analog input 3 is scaled to the voltage in AI3LowVal (13.10).
Notes:
−
AI3LowVal (13.10) is only valid if ConvModeAI3 (13.11) =
±
10V Bi.
−
Can only be used for voltage measurement.
Int. Scaling: 1 == 1 mV
Type: SI
Volatile:
N
-10000
10000
-10000
mV
13.11 ConvModeAI3 (conversion mode analog input 3)
Analog input 3 on the SDCS-CON-F is only working with voltage:
0 =
±
10V Bi
-10 V to 10 V, default
1 = 0V-10V Uni
0 V to 10 V unipolar input
2 = 2V-10V Uni
2 V to 10 V unipolar input
3 = 5V Offset
5 V offset in the range 0 V to 10 V for testing or indication of bipolar signals (e.g. torque,
speed, etc.)
4 = 6V Offset
6 V offset in the range 2 V to 10 V for testing or indication of bipolar signals (e.g. torque,
speed, etc.)
Int. Scaling: 1 == 1
Type: C
Volatile:
N
±
1
0
V Bi
6
V
O
ffs
e
t
±
1
0
V Bi
-
13.12 FilterAI3 (filter time analog input 3)
Analog input 3 filter time. The hardware filter time is
≤
2 ms.
Int. Scaling: 1 == 1 ms
Type: I
Volatile:
N
0
10000
0
ms
13.13 AI4HighVal (analog input 4 high value)
+100 % of the input signal connected to analog input 4 is scaled to the voltage in AI4HighVal (13.13).
Note:
Can only be used for voltage measurement.
Int. Scaling: 1 == 1 mV
Type: I
Volatile:
N
-10000
10000
10000
mV
13.14 AI4LowVal (analog input 4 low value)
-100 % of the input signal connected to analog input 4 is scaled to the voltage in AI4LowVal (13.14).
Notes:
−
AI3LowVal (13.14) is only valid if ConvModeAI4 (13.15) =
±
10V Bi.
−
Can only be used for voltage measurement.
Int. Scaling: 1 == 1 mV
Type: SI
Volatile:
N
-10000
10000
-10000
mV
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...