t
11.14 MotPotDown (motor pot down)
With the motor pot down function, the motor speed is decreased by means of the selected binary input.
DecTime1 (22.02) limits the deceleration until zero speed or MotPotMin (11.15) is reached. MotPotDown
(11.14) overrides MotPotUp (11.13):
0 = NotUsed default
1 = DI1
1= decrease speed, 0 = hold speed
2 = DI2
1= decrease speed, 0 = hold speed
3 = DI3
1= decrease speed, 0 = hold speed
4 = DI4
1= decrease speed, 0 = hold speed
5 = DI5
1= decrease speed, 0 = hold speed
6 = DI6
1= decrease speed, 0 = hold speed
7 = DI7
1= decrease speed, 0 = hold speed
8 = DI8
1= decrease speed, 0 = hold speed
9 = DI9
1= decrease speed, 0 = hold speed, only available with digital extension board
10 = DI10
1= decrease speed, 0 = hold speed, only available with digital extension board
11 = DI11
1= decrease speed, 0 = hold speed, only available with digital extension board
12 = MCW Bit11
1= decrease speed, 0 = hold speed, MainCtrlWord (7.01) bit 11
13 = MCW Bit12
1= decrease speed, 0 = hold speed, MainCtrlWord (7.01) bit 12
14 = MCW Bit13
1= decrease speed, 0 = hold speed, MainCtrlWord (7.01) bit 13
15 = MCW Bit14
1= decrease speed, 0 = hold speed, MainCtrlWord (7.01) bit 14
16 = MCW Bit15
1= decrease speed, 0 = hold speed, MainCtrlWord (7.01) bit 15
17 = DI1 + Stop
DI1 = 1 OR Stop command active => decrease speed, 0 = hold speed
18 = DI2 + Stop
DI1 = 1 OR Stop command active => decrease speed, 0 = hold speed
19 = DI3 + Stop
DI1 = 1 OR Stop command active => decrease speed, 0 = hold speed
20 = DI4 + Stop
DI1 = 1 OR Stop command active => decrease speed, 0 = hold speed
21 = DI5 + Stop
DI1 = 1 OR Stop command active => decrease speed, 0 = hold speed
22 = DI6 + Stop
DI1 = 1 OR Stop command active => decrease speed, 0 = hold speed
23 = DI7 + Stop
DI1 = 1 OR Stop command active => decrease speed, 0 = hold speed
24 = DI8 + Stop
DI1 = 1 OR Stop command active => decrease speed, 0 = hold speed
Note:
The speed reference is selected by means of Ref1Sel (11.03) = MotPot respectively Ref2Sel (11.06) =
MotPot.
Int. Scaling: 1 == 1
Type: C
Volatile:
N
No
tUs
e
d
D
I8
+
S
to
p
No
tUs
e
d
11.15 MotPotMin (motor pot minimum)
The motor pot minimum function sets the minimum speed limit defined by FixedSpeed1 (23.02). When the
drive is started the motor accelerates to FixedSpeed1 (23.02). It is not possible to set the speed below
FixedSpeed1 (23.02) by means of the motor pot function:
0 = NotUsed default
1 = DI1
1= released, 0 = blocked
2 = DI2
1= released, 0 = blocked
3 = DI3
1= released, 0 = blocked
4 = DI4
1= released, 0 = blocked
5 = DI5
1= released, 0 = blocked
6 = DI6
1= released, 0 = blocked
7 = DI7
1= released, 0 = blocked
8 = DI8
1= released, 0 = blocked
9 = DI9
1= released, 0 = blocked, only available with digital extension board
10 = DI10
1= released, 0 = blocked, only available with digital extension board
11 = DI11
1= released, 0 = blocked, only available with digital extension board
12 = MCW Bit11
1= released, 0 = blocked, MainCtrlWord (7.01) bit 11
13 = MCW Bit12
1= released, 0 = blocked, MainCtrlWord (7.01) bit 12
14 = MCW Bit13
1= released, 0 = blocked, MainCtrlWord (7.01) bit 13
15 = MCW Bit14
1= released, 0 = blocked, MainCtrlWord (7.01) bit 14
16 = MCW Bit15
1= released, 0 = blocked, MainCtrlWord (7.01) bit 15
Int. Scaling: 1 == 1
Type: C
Volatile:
N
No
tUs
e
d
M
C
W
B
it
15
No
tUs
e
d
Group 12: Constant speeds
12.01 Unused
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...