Parameters 281
Average
The current energy monitoring period (parameter
) is compared to the average of the two previous
periods (
and
3
83.02
Mon period
Defines the length of an energy monitoring period. The first
period starts when the drive is powered up.
0.00 … 35791394.11
h
Length of monitoring period.
1 = 1 min
83.03
kWh limit
Consumed energy limit for parameter
, selection
0…2147483647
kWh
Energy limit.
1 = 1 kWh
83.04
Mon tolerance
Tolerance for energy limit. The energy consumption may
exceed the reference energy by this tolerance value until the
action defined by parameter
is taken.
0…2147483647
kWh
Tolerance.
1 = 1 kWh
83.05
Energy mon ctrl
Defines the action that is taken if the energy consumption
exceeds the tolerance limits.
Not sel
No action taken.
0
Alarm
The drive generates alarm
1
83.06
Energy reset
Resets the energy monitoring counters.
No
No reset. The parameter automatically reverts to this value
after a reset.
0
Period
Resets the periodic energy counters (parameters
1
Month
Resets the monthly energy counters (parameters
2
94
94 Ext IO conf
I/O extension configuration.
94.01
Ext IO1 sel
Activates an I/O extension installed into Slot 1. Depending
on the module used, enables
• digital input DI7
• digital input/outputs DIO3…DIO6
• analog inputs AI3…AI5
• analog output AO3 or
• relay outputs RO3…RO6.
None
No extension installed into Slot 1.
0
FIO-01
FIO-01 extension installed into Slot 1. Additional 4 × DIO
and 2 × RO are in use.
1
FIO-11
FIO-11 extension installed into Slot 1. Additional 2 × DIO,
3 × AI and 1 × AO are in use.
2
FIO-21
FIO-21 extension installed into Slot 1. Additional 1 × DI,
1 × AI and 2 × RO are in use.
3
FIO-31
FIO-31 extension installed into Slot 1. Additional 4 × RO are
in use.
4
95
95 Hw configuration
Diverse hardware-related settings.
95.01
Ctrl boardSupply
Selects how the drive control unit is powered.
No.
Name/Value
Description
FbEq
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...