208 Parameters
35.02
Signal1 max
Defines the real value of the selected signal that
corresponds to the maximum display value defined by
parameter
.
-32768…32768
Real signal value corresponding to maximum process
variable 1 value.
1 = 1
35.03
Signal1 min
Defines the real value of the selected signal that
corresponds to the minimum display value defined by
parameter
. See diagram at parameter
.
-32768…32768
Real signal value corresponding to minimum process
variable 1 value.
1 = 1
35.04
Proc var1 dispf
Scaling for process variable 1. This setting also scales the
value for fieldbus.
0
1 = 1
0
1
10 = 1
1
2
100 = 1
2
3
1000 = 1
3
4
10000 = 1
4
5
100000 = 1
5
35.05
Proc var1 unit
Specifies the unit for parameter
(process
variable 1).
0
None
0
1
A
1
2
V
2
3
Hz
3
4
%
4
5
s
5
6
h
6
7
rpm
7
8
kh
8
9
C
9
10
lbft
10
11
mA
11
No.
Name/Value
Description
FbEq
Signal selected by
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...