Parameters 123
03
03 Control values
Speed and torque control values.
03.03
SpeedRef unramp
Used speed reference ramp input in rpm.
100 = 1 rpm
03.05
SpeedRef ramped
Ramped and shaped speed reference in rpm.
100 = 1 rpm
03.06
SpeedRef used
Used speed reference in rpm (reference before speed error
calculation).
100 = 1 rpm
03.07
Speed error filt
Filtered speed error value in rpm.
100 = 1 rpm
03.08
Acc comp torq
Output of the acceleration compensation (torque in percent). 10 = 1%
03.09
Torq ref sp ctrl
Limited speed controller output torque in percent.
10 = 1%
03.13
Torq ref to TC
Torque reference in percent for the torque control.
10 = 1%
03.14
Torq ref used
Torque reference after frequency, voltage and torque
limiters. 100% corresponds to the motor nominal torque.
10 = 1%
03.17
Flux actual
Actual flux reference in percent.
1 = 1%
03.20
Max speed ref
Maximum speed reference.
100 = 1 rpm
03.21
Min speed ref
Minimum speed reference.
100 = 1 rpm
04
04 Appl values
Process and counter values.
04.01
Act val
Final actual value after selection (see parameter group
). The unit and scaling are defined by parameters
respectively.
-
04.02
Setpoint
Final setpoint (reference) value after selection (see
parameter group
). The unit and scaling are
and
respectively.
-
04.04
Process PID err
Process PID error, i.e. difference between PID setpoint and
actual value.
10 = 1%
04.05
Process PID out
Output of the process PID controller.
10 = 1%
04.06
Process var1
Process variable 1. See parameter group
1000 = 1%
04.07
Process var2
Process variable 2. See parameter group
1000 = 1%
04.08
Process var3
Process variable 3. See parameter group
1000 = 1%
04.09
Counter ontime1
Reading of on-time counter 1. See parameter
. Can be reset by entering a 0.
1 = 1 s
04.10
Counter ontime2
Reading of on-time counter 2. See parameter group
. Can be reset by entering a 0.
1 = 1 s
04.11
Counter edge1
Reading of rising edge counter 1. See parameter group
. Can be reset by entering a 0.
1 = 1
04.12
Counter edge2
Reading of rising edge counter 2. See parameter group
. Can be reset by entering a 0.
1 = 1
04.13
Counter value1
Reading of value counter 1. See parameter group
. Can be reset by entering a 0.
1 = 1
04.14
Counter value2
Reading of value counter 2. See parameter group
. Can be reset by entering a 0.
1 = 1
04.20
Act val 1 out
Actual value 1 (selected by parameter
).
100 = 1 unit
No.
Name/Value
Description
FbEq
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...