136 Parameters
In1St In2Dir
The source selected by
is the start signal
(0 = stop, 1 = start), the source selected by
is the direction signal (0 = forward, 1 = reverse).
6
10.02
Ext1 start in1
Selects source 1 of start and stop commands for external
control location EXT1. See parameter
selections
Note:
This parameter cannot be changed while the drive is
running.
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DIO4
Digital input/output DIO4 (as indicated by
,
bit 3).
1073938947
Timed func
Bit 4 of parameter
. The bit is on when
at least one of the four timers configured in parameter group
is on.
1074005518
Const
Constant and bit pointer settings (see
on page
-
Pointer
10.03
Ext1 start in2
Selects source 2 of start and stop commands for external
control location EXT1. See parameter
Note:
This parameter cannot be changed while the drive is
running.
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
DIO5
Digital input/output DIO5 (as indicated by
,
bit 4).
1074004483
Const
Bit pointer setting (see
on page
).
-
Pointer
10.04
Ext2 start func
Selects the source of start and stop commands for external
control location 2 (EXT2).
Note:
This parameter cannot be changed while the drive is
running.
Not sel
No start or stop command sources selected.
0
In1
The source of the start and stop commands is selected by
parameter
. The state transitions of the
source bit are interpreted as follows:
1
3-wire
The sources of the start and stop commands is selected by
parameters
The state transitions of the source bits are interpreted as
follows:
2
No.
Name/Value
Description
FbEq
State of source
(via par
Command
0 -> 1
Start
1 -> 0
Stop
State of source 1
)
State of source 2
)
Command
0 -> 1
1
Start
Any
1 -> 0
Stop
Any
0
Stop
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...