Parameters 283
0.00 …100000.00
mH
Leakage inductance.
100 = 1 mH
99
99 Start-up data
Language selection, motor configuration and ID run settings.
99.01
Language
Selects the language of the control panel displays.
Note:
Not all languages listed below are necessarily
supported.
English
English.
0809
Deutsch
German.
0407
Italiano
Italian.
0410
Espanol
Spanish.
040A
Nederlands
Dutch.
0413
Francais
French.
040C
Dansk
Danish.
0406
Russki
Russian.
0419
Polski
Polish.
0415
Turkce
Turkish.
041F
Magyar
Hungarian.
040E
99.05
Motor ctrl mode
Selects the motor control mode.
DTC
Direct torque control. This mode is suitable for most
applications.
Note:
Instead of direct torque control, use scalar control
• with multimotor applications 1) if the load is not equally
shared between the motors, 2) if the motors are of
different sizes, or 3) if the motors are going to be changed
after the motor identification (ID run),
• if the nominal current of the motor is less than 1/6 of the
nominal output current of the drive,
• if the drive is used with no motor connected (for example,
for test purposes),
• if the drive runs a medium-voltage motor through a step-
up transformer.
0
Scalar
Scalar control. This mode is suitable in special cases where
DTC cannot be applied. In scalar control, the drive is
controlled with a frequency reference. The outstanding
motor control accuracy of DTC cannot be achieved in scalar
control. Some standard features are disabled in scalar
control mode.
Note:
Correct motor run requires that the magnetizing
current of the motor does not exceed 90% of the nominal
current of the inverter.
See also section
on page
1
99.06
Mot nom current
Defines the nominal motor current. Must be equal to the
value on the motor rating plate. If multiple motors are
connected to the drive, enter the total current of the motors.
Notes:
• Correct motor run requires that the magnetizing current of
the motor does not exceed 90% of the nominal current of
the drive.
• This parameter cannot be changed while the drive is
running.
No.
Name/Value
Description
FbEq
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...