194 Parameters
AI3 scaled
(see page
).
1073742345
AI4 scaled
(see page
).
1073742347
AI5 scaled
(see page
).
1073742349
FBA setpoint
1073742376
Shared sig2
).
1073742380
Int set 2
(see below).
1073749253
Pointer
Value pointer setting (see
on page
).
-
29.04
Internal set 1
Defines process setpoint 1 when parameter
is set to
.
0.00 … 32768.00%
Internal process setpoint 1.
100 = 1%
29.05
Internal set 2
Defines process setpoint 2 when parameter
is set to
.
0.00 … 32768.00%
Internal process setpoint 2.
100 = 1%
29.06
Reference step 1
Sets a percentage that is added to the process setpoint
when one auxiliary (direct-on-line) motor is running.
Example:
The drive operates three parallel pumps that pump
water into a pipe. The pressure in the pipe is controlled. The
constant pressure reference is set by parameter
. During low water consumption, only the
speed-regulated pump is run. When water consumption
increases, constant-speed (direct-on-line) pumps are
started: first one pump, and if the demand grows further, also
the other pump. As water flow increases, the pressure loss
between the beginning (point of measurement) and the end
of the pipe increases. By setting suitable reference steps,
the process setpoint is increased along with the increasing
pumping capacity. The reference steps compensate the
growing pressure loss and prevent the pressure fall at the
end of the pipe.
0.00 … 100.00%
Reference step 1.
100 = 1%
29.07
Reference step 2
Sets a percentage that is added to the process setpoint
when two auxiliary (direct-on-line) motors are running. See
parameter
0.00 … 100.00%
Reference step 2.
100 = 1%
29.08
Reference step 3
Sets a percentage that is added to the process setpoint
when three auxiliary (direct-on-line) motors are running. See
parameter
0.00 … 100.00%
Reference step 3.
100 = 1%
29.09
Reference step 4
Sets a percentage that is added to the process setpoint
when four auxiliary (direct-on-line) motors are running. See
parameter
0.00 … 100.00%
Reference step 4.
100 = 1%
29.10
Reference step 5
Sets a percentage that is added to the process setpoint
when five auxiliary (direct-on-line) motors are running. See
parameter
0.00 … 100.00%
Reference step 5.
100 = 1%
No.
Name/Value
Description
FbEq
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...