254 Parameters
77
77 Pump sleep
Sleep function settings.
See also section
on page
.
77.01
Sleep mode sel
Enables/disables the sleep function.
Not used
Sleep function disabled.
0
Internal
The signal selected by parameter
If the signal
remains below this value longer than the sleep delay (
), the drive shifts to sleep mode.
The sleep and wake-up delays (
) are in force.
1
External
The sleep function is activated by the source selected by
parameter
The sleep delay (
) is not in force but the
wake-up delay (
) is.
2
Int+ext
When the source selected by parameter
is “1”, the sleep function works as with the setting
.
When the source selected by parameter
is “0”, the sleep function is disabled.
3
Soft ext
When the source selected by parameter
is “0”, the sleep function is disabled.
When the source selected by parameter
is “1”, the input of the PID controller is set to 0. After the drive
enters sleep mode, it will not wake up until the signal returns
to “0”.
4
77.02
Sleep int sel
Selects the internal signal to be monitored by the sleep
function when parameter
is set to
.
Speed
).
1073742081
Speed %
(see page
1073742082
AI1
(see page
1073742340
AI1 scaled
(see page
).
1073742341
AI2
(see page
1073742342
AI2 scaled
(see page
).
1073742343
Proc act
(see page
).
1073742849
Flow act
(see page
).
1073743109
Pointer
Value pointer setting (see
on page
).
-
77.03
Sleep level
Defines the start limit for the sleep function when parameter
is set to
,
or
.
-32768.00 …
32768.00
Sleep start level.
100 = 1
77.04
Sleep delay
Defines the delay for the sleep start function. See parameter
. When the monitored signal falls below the
sleep level, the counter starts. When the signal exceeds the
sleep level, the counter resets.
0 … 12600 s
Sleep start delay.
1 = 1 s
No.
Name/Value
Description
FbEq
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...