Control through the embedded fieldbus interface 347
Modbus register addresses for the ABB Drives enhanced profile
Register address Register data (16-bit words)
400001
Fieldbus control word (CW). See section
Control word for the ABB Drives
400002
Fieldbus reference 1 (REF1).
400003
Fieldbus reference 2 (REF2
400004
Fieldbus data in/out 1 (Drive parameter
…
…
400015
Fieldbus data in/out 12 (Drive parameter
58.46 Data I/O 12
)
400051
Fieldbus status word (SW). See section
Status word for the ABB Drives
400052
Fieldbus actual value 1 (ACT1)
400053
Fieldbus actual value 2 (ACT2)
40054
Fieldbus data in/out 13 (Drive parameter
58.47 Data I/O 12
)
…
…
40065
Fieldbus data in/out 24 (Drive parameter
400101…409999
Register address (16-bit drive parameter) = 100
×
group +
index
Example: Modbus register address to drive parameter 03.18 is
100
×
3 + 18 = 400318
Drive parameter access (32-bit drive parameter) = 200
×
group
+ 2
×
index
Example: Modbus register address to drive parameter 01.27
200
×
1 + 2
×
27 = 420254
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...