Parameters 279
82.02
Fwd step
Forward step frequency for the cleaning sequence in percent
of the value of parameter
.
0.0 … 100.0%
Forward step frequency.
10 = 1%
82.03
Rev step
Reverse step frequency for the cleaning sequence in
percent of the value of parameter
.
0.0 … 100.0%
Reverse step frequency.
10 = 1%
82.04
Off time
Interval between forward and reverse steps during the
cleaning sequence.
0…1000 s
Interval between steps.
1 = 1 s
82.05
Fwd step time
Duration of each forward step during the cleaning sequence.
0…1000 s
Duration of each forward step.
1 = 1 s
82.06
Rev step time
Duration of each reverse step during the cleaning sequence.
0…1000 s
Duration of each reverse step.
1 = 1 s
82.07
Time trig
Time between periodical cleaning sequences. See
parameter
, bit 3.
0.00 … 35791394.11
h
Time between cleaning sequences.
1 = 1 min
82.08
Nbr of steps
Number of forward-reverse step combinations to be
performed during the cleaning sequence.
0…2147483647
Number of steps.
1 = 1
82.09
Supervis source
Defines a signal that triggers the cleaning sequence when it
remains above the limit defined by parameter
for longer than the time set by parameter
.
, bit 4.
Current A
(see page
).
1073742084
Current %
(see page
).
1073742085
Pointer
Value pointer setting (see
on page
-
82.10
Supervis limit
Defines a limit for the signal selected by parameter
0.0 … 32767.0
Cleaning sequence triggering limit.
10 = 1
No.
Name/Value
Description
FbEq
Bit
Name
Function
0
Enabled
0 = No: Cleaning sequence disabled.
1 = Yes: Cleaning sequence enabled.
1
Master enb
0 = No: Cleaning sequence not allowed when the drive is master.
1 = Yes: Cleaning sequence allowed when the drive is master.
2
Follower enb
0 = No: Cleaning sequence not allowed when the drive is a follower.
1 = Yes: Cleaning sequence allowed when the drive is a follower.
3
Time trig
1 = Enable: Cleaning sequence starts periodically at intervals defined by
parameter
.
4
Supervision
1 = Enable: The cleaning sequence is started whenever the signal selected
by parameter
exceeds the value of parameter
5
At start
1 = Enable: Cleaning sequence performed on every start command.
6
Trig ptr
1 = Enable: The cleaning sequence is performed when the signal selected
by parameter
changes to 1.
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...