Parameters 261
Const
Bit pointer setting (see
on page
-
Pointer
78.11
Interlock pump 6
Selects the input (or signal) for status of pump 6.
When the input is 1, the drive assumes the pump is in use
and can be started.
Not used
The interlock is off, meaning that the pump is not in use.
0
On
The interlock is on, meaning that the pump is ready for use.
1
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
Const
Bit pointer setting (see
on page
-
Pointer
78.12
Interlock pump 7
Selects the input (or signal) for status of pump 7.
When the input is 1, the drive assumes the pump is in use
and can be started.
Not used
The interlock is off, meaning that the pump is not in use.
0
On
The interlock is on, meaning that the pump is ready for use.
1
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
Const
Bit pointer setting (see
on page
-
Pointer
78.13
Interlock pump 8
Selects the input (or signal) for status of pump 8.
When the input is 1, the drive assumes the pump is in use
and can be started.
Not used
The interlock is off, meaning that the pump is not in use.
0
On
The interlock is on, meaning that the pump is ready for use.
1
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
Const
Bit pointer setting (see
on page
-
Pointer
78.14
Runtime change
Enables the reset, or arbitrary setting, of
.
No
The parameter automatically reverts to this value.
0
Set
Enables the setting of
to an arbitrary
value.
1
No.
Name/Value
Description
FbEq
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...