148 Parameters
Last speed
The drive generates an
alarm
and freezes the speed to the level the drive was operating at.
The speed is determined by the average speed over the
previous 10 seconds.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
3
13.33
AI superv cw
Selects the analog input signal supervision limit.
Example:
If parameter value is set to 0b0010, bit 1
is selected.
14
14 Digital I/O
Configuration of digital input/outputs, relay outputs, the
frequency input, and the frequency output.
14.01
DI invert mask
Inverts status of digital inputs as reported by
14.02
DIO1 conf
Selects whether DIO1 is used as a digital output or input.
Output
DIO1 is used as a digital output.
0
Input
DIO1 is used as a digital input.
1
Freq input
DIO1 is used as a frequency input.
2
14.03
DIO1 out src
Selects a drive signal to be connected to digital output DIO1
(when
is set to
).
Trad pump7
Bit 6 of
(see page
1074136322
Trad pump8
Bit 7 of
(see page
1074201858
Ready
Bit 0 of
(see page
).
1073743361
Enabled
Bit 1 of
(see page
).
1073808897
Started
Bit 2 of
(see page
).
1073874433
Running
Bit 3 of
(see page
).
1073939969
Alarm
Bit 7 of
(see page
).
1074202113
Ext2 active
Bit 8 of
(see page
).
1074267649
Fault
).
1074398721
No.
Name/Value
Description
FbEq
Bit
Supervision
Action selected by parameter
is taken if
0
AI1 min sup
AI1 signal value falls below the value defined by equation: par.
- 0.5 mA or V
1
AI1 max sup
AI1 signal value exceeds the value defined by equation: par.
+ 0.5 mA or V
2
AI2 min sup
AI2 signal value falls below the value defined by equation: par.
- 0.5 mA or V
3
AI2 max sup
AI1 signal value exceeds the value defined by equation: par.
+ 0.5 mA or V
Bit
Name
0
1 = Invert DI1
1
1 = Invert DI2
2
1 = Invert DI3
3
1 = Invert DI4
4
1 = Invert DI5
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...