Parameters 147
13.24
AI5 max scale
Defines the real value that corresponds to the maximum
analog input AI5 value defined by parameter
-32768.000 …
32768.000
Real value corresponding to maximum AI5 value.
1000 = 1
13.25
AI5 min scale
Defines the real value that corresponds to the minimum
analog input AI5 value defined by parameter
See the drawing at parameter
.
-32768.000 …
32768.000
Real value corresponding to minimum AI5 value.
1000 = 1
13.31
AI tune
Triggers the AI tuning function.
Connect the signal to the input and select the appropriate
tuning function.
No action
AI tune is not activated.
0
AI1 min tune
Current analog input AI1 signal value is set as minimum
value of AI1 into parameter
. The value reverts
back to
automatically.
1
AI1 max tune
Current analog input AI1 signal value is set as maximum
value of AI1 into parameter
. The value reverts
back to
automatically.
2
AI2 min tune
Current analog input AI2 signal value is set as minimum
value of AI2 into parameter
. The value reverts
back to
automatically.
3
AI2 max tune
Current analog input AI2 signal value is set as maximum
value of AI2 into parameter
. The value reverts
back to
automatically.
4
13.32
AI superv func
Selects how the drive reacts when analog input signal limit is
reached. The limit is selected by parameter
No
No action taken.
0
Fault
The drive trips on an
fault.
1
Spd ref Safe
The drive generates an
alarm
and sets the speed to the speed defined by parameter
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
2
No.
Name/Value
Description
FbEq
AI
(scaled)
AI
(mA/V)
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...