266 Parameters
79.08
Start 3 level
Defines the start level for pump 3. This is also the stop level
for the pump unless
. See the diagrams at parameter
.
0.00 … 32768.00%
Start level for pump 3.
TBA
79.09
Start 4 level
Defines the start level for pump 4. This is also the stop level
for the pump unless
. See the diagrams at parameter
.
0.00 … 32768.00%
Start level for pump 4.
TBA
79.10
Start 5 level
Defines the start level for pump 5. This is also the stop level
for the pump unless
. See the diagrams at parameter
.
0.00 … 32768.00%
Start level for pump 5.
TBA
79.11
Start 6 level
Defines the start level for pump 6. This is also the stop level
for the pump unless
. See the diagrams at parameter
.
0.00 … 32768.00%
Start level for pump 6.
TBA
79.12
Start 7 level
Defines the start level for pump 7. This is also the stop level
for the pump unless
. See the diagrams at parameter
.
0.00 … 32768.00%
Start level for pump 7.
TBA
79.13
Start 8 level
Defines the start level for pump 8. This is also the stop level
for the pump unless
. See the diagrams at parameter
.
0.00 … 32768.00%
Start level for pump 8.
TBA
79.14
High level
In emptying mode, when the measured level exceeds this
value, all pumps start running at the speed defined by
parameter
In filling mode, when the measured level exceeds this value,
all pumps stop (if not stopped already).
0.00 … 32768.00%
High level.
TBA
79.15
High switch
Selects a digital source that is used to determine that the
liquid level in the container has risen very high. When the
source switches on, an alarm,
is given. The
alarm is cleared when the source switches off.
Not used
No high switch used.
0
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
Const
Bit pointer setting (see
on page
).
-
Pointer
No.
Name/Value
Description
FbEq
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...