Parameters 265
79.02
Stopping mode
Selects whether the pumps are stopped simultaneously or
individually.
Stable level
When the start level of a pump (parameters
) is reached, the master drive waits
for the level delay (parameter
) to
elapse, then stops the pump.
0
Common stop
All the pumps running will continue to run until the stop level
(parameter
) is reached. All pumps will then
be stopped one by one at intervals defined by parameter
.
1
79.03
Low level
Defines the low level for level control.
In emptying mode, when the measured level falls below the
low level, all pumps stop (if not stopped already).
In filling mode, when the measured level falls below the low
level, all pumps start running at the speed defined by
parameter
See the diagrams at parameter
0.00 … 32768.00%
Low level.
TBA
79.04
Low switch
Selects a digital source that is used to determine that the
liquid level in the container has fallen very low. When the
source becomes active (1), an alarm,
is
given. The alarm is cleared when the source switches off.
Not used
No low switch used.
0
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
Const
Bit pointer setting (see
on page
-
Pointer
79.05
Stop level
Defines the stop level for the pump station.
If parameter
is set to
,
pumps 3 and 2, for example, are stopped when
and
are reached respectively; pump
1 is stopped at the stop level.
If parameter
, all
pumps will continue to run until the stop level is reached.
See the diagrams at parameter
0.00 … 32768.00%
Stop level.
TBA
79.06
Start 1 level
Defines the start level for pump 1. See the diagrams at
parameter
0.00 … 32768.00%
Start level for pump 1.
TBA
79.07
Start 2 level
Defines the start level for pump 2. This is also the stop level
for the pump unless
. See the diagrams at parameter
.
0.00 … 32768.00%
Start level for pump 2.
TBA
No.
Name/Value
Description
FbEq
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...