Parameters 129
06.07
Torq lim status
Torque controller limitation status word.
-
06.12
Op mode ack
Operation mode acknowledge: 0 = Stopped, 1 = Speed,
10 = Scalar, 11 = Forced Magn (i.e. DC Hold)
1 = 1
06.13
Superv status
Supervision status word. Bits 0…2 reflect the status of
supervisory functions 1…3 respectively. The functions are
configured in parameter group
-
06.14
Timed func stat
Bits 0…3 show the on/off status of the four timers (1…4
respectively) configured in parameter group
(page
). Bit 4 is on if any one of the four timers
is on.
-
06.15
Counter status
Counter status word. Shows whether the maintenance
counters configured in parameter group
(page
) have exceeded their limits.
-
No.
Name/Value
Description
FbEq
Bit
Name
Information
0
Undervolt-
age
1 = Intermediate circuit DC undervoltage. *
1
Overvoltage 1 = Intermediate circuit DC overvoltage. *
2…3
Reserved
4
Internal cur-
rent
1 = An inverter current limit is active. The limit is identified by bits 8…11.
5
Reserved
6
Motor pull-
out
1 = Motor pull-out limit is active, i.e. the motor cannot produce more torque.
7
Reserved
8
Thermal
1 = Input current is limited by main circuit thermal limit.
9
INU maxi-
mum
1 = Inverter maximum output current limit is active (limits the drive output
current
I
MAX
). **
10
User cur-
rent
1 = Maximum inverter output current limit is active. The limit is defined by
parameter
. **
11
Thermal
IGBT
1 = Calculated thermal current value limits the inverter output current. **
12…15 Reserved
* One of bits 0…3 can be on simultaneously. The bit typically indicates the limit that is exceeded
first.
** Only one of bits 9…11 can be on simultaneously. The bit typically indicates the limit that is
exceeded first.
Bit
Name
Information
0
Ontime1
1 = On-time counter 1 has reached its preset limit.
1
Ontime2
1 = On-time counter 2 has reached its preset limit.
2
Edge1
1 = Rising edge counter 1 has reached its preset limit.
3
Edge2
1 = Rising edge counter 2 has reached its preset limit.
4
Value1
1 = Value counter 1 has reached its preset limit.
5
Value2
1 = Value counter 2 has reached its preset limit.
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...