Parameters 171
20.03
Pos speed ena
Selects the source of the positive speed reference enable
command.
1 = Positive speed reference is enabled.
0 = Positive speed reference is interpreted as zero speed
reference (In the figure below
is set
to zero after the positive speed enable signal has cleared).
The speed reference is set to zero and the motor is stopped
along the currently active deceleration ramp.
Example:
The motor is rotating in the forward direction. To
stop the motor, the positive speed enable signal is
deactivated by a hardware limit switch (e.g. via a digital
input). If the positive speed enable signal remains
deactivated and the negative speed enable signal is active,
only reverse rotation of the motor is allowed.
Const
Bit pointer setting (see
on page
-
Pointer
20.04
Neg speed ena
Selects the source of the negative speed reference enable
command. See parameter
.
Const
Bit pointer setting (see
on page
-
Pointer
20.05
Maximum current
Defines the maximum allowed motor current.
0.00 … 30000.00 A
Maximum motor current.
100 = 1 A
20.06
Torq lim sel
Defines a source that selects between the two sets of torque
limits defined by parameters
0 = The torque limits defined by parameters
are in force.
1 = The torque limits defined by parameters
are in force.
Const
Bit pointer setting (see
on page
-
Pointer
20.07
Maximum torque1
Defines maximum torque limit 1 for the drive (in percent of
the motor nominal torque). See parameter
0.0 … 1600.0%
Maximum torque 1.
10 = 1%
20.08
Minimum torque1
Defines minimum torque limit 1 for the drive (in percent of
the motor nominal torque). See parameter
-1600.0 … 0.0%
Minimum torque 1.
10 = 1%
No.
Name/Value
Description
FbEq
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...